Download Print this page

Bosch D7212GV2 Release Notes page 5

Version 7.07
Hide thumbs Also See for D7212GV2:

Advertisement

Corrections now prevent the D7212GV2 Control
Panel from performing a watchdog reset when an
A # Area Type
area with an
individually armed. Shared areas should not be
individually armed or disarmed.
Corrections now prevent a duress passcode from
being accepted by a keypad currently in an area
A# Duress Enable
that has
Duress feature is used, A
be set to Yes for all areas.
The alternate function of Area 6 Silent Alarm
Relay parameter was removed. To enable Fire
Trouble Resound support, use
GV2AUX→MISCELLANEOUS→Fire Trouble
Resound.
The alternate function of Area 5 Silent Alarm
Relay parameter was removed. The Ground Fault
detection feature is solely enabled by closing
Switch S4 on the D7212GV2 Control Panel.
Changes now suppress the ALARM SILENCED
message when a user attempts to silence a Ring
Until Restored fire bell. A fire alarm generated by
a point with the Ring Until Restored (
Rst
) feature set to Yes will sustain the fire bell
until the sensor is restored.
Corrections ensure that acknowledged Silent
Alarms scroll correctly on the idle text displays on
the D1260 and D1260B Keypads.
Corrections now allow a user's token, with
Disarm Level
set to I, to disarm the interior of all
areas within the scope of the keypad programmed
D# CC# Scope
at
. The keypad programmed at
D# CC# Scope
must have
Follows Scope
set to Yes to disarm the interior of
all areas within scope.
Corrections now allow the panel-wide
Communications Failure Relay output to activate
when events in Route Groups 2 through 4 do not
reach the central station. Previously this relay
output activated only on a communication failure
for Route Group 1.
© 2007 Bosch Security Systems, Inc.
set to Shared is
set to No. If the
# Duress Enable
should
P# Ring Til
L#
CC# Passcode
D7212GV2 Release Notes for Version 7.07
2.5
Version 7.02
The Phone Line Supervision feature has improved
accuracy in detecting the phone line.
2
The Modem IIIa
same ID as the G Series control panels, allowing
compatibility with non-Bosch central station
receivers.
2.6
Version 7.01
The following are corrections and changes made since
Version 6.60 in the G Series Control Panels.
The GV2 Series Control Panels have the same
response to low AC voltage as to an AC failure.
If the control panel battery is detected as missing,
the Walk Test function skips the Battery Test.
Several system stability issues are fixed to prevent
erroneous Parameter Checksum Failures.
The Service Walk Test on the D7212GV2 now
shows the correct maximum number of points in
the system.
The Telephone Ground Start circuitry and
associated programming prompts are removed
from the GV2 Series Control Panels.
The GV2 Series Control Panels require the D6500
receiver to have a D6511 MPU card at version
1.06 or above for maximum communication
efficiency.
The Extend Close (COMMAND 51) feature was
modified to prevent the new Close Window time
from setting to a value earlier than the current
time.
When disarming an area with
enabled, the keypad waits for the time equal to
the exit delay for the area. If the second passcode
is not entered before the prompt times out, then
the rule resets and waits for the first passcode
again.
Several changes in this release prevent local alarm
events from being sent intermittently to the
central station. All local alarm events should now
remain local.
Page 5
D7212GV2
product ID is changed to the
Two Man Rule
F01U009079-04

Advertisement

loading