Input Over Current Detection - Daikin D-Series Service Manual

Super multi nx d/e series
Hide thumbs Also See for D-Series:
Table of Contents

Advertisement

Si12-619A
5.15

Input Over Current Detection

E8
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
Malfunction is detected by checking the input current value.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Service Diagnosis
1
2
3
4
5
1
4
1
The input current is a certain value (depending on the model) or over for 2.5 seconds.
The compressor halts if the error occurs, and restarts automatically after 3 minutes stand-by.
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective inverter main circuit electrolytic capacitor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit
4
Troubleshooting
229