Input Over Current Detection - Daikin ATXS35EV1B7 Service Manual

Inverter pair e-series
Hide thumbs Also See for ATXS35EV1B7:
Table of Contents

Advertisement

Troubleshooting
4.12

Input Over Current Detection

4.12.1 25/35 Class
E8
Remote
Controller
Display
Method of
An input over-current is detected by checking the input current value with the compressor
running.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.07
Refer to P.131
Check No.08
Refer to P.131
96
The following current with the compressor running continues for 2.5 seconds.
Cooling / Heating: Above 9.25A
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
∗ An input over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input over-current,
take the following procedure.
Get restarted and measure the
input current.
Input current flowing
above its stop level?
YES
Turn off the power and disconnect
the harnesses U, V and W.
Check with the inverter checker (∗).
Any LED off?
NO
Turn off the power, and reconnect
the harnesses. Turn on the power
again and get restarted.
Check No. 08
Check the discharge pressure.
Check No. 07
Check the installation condition.
NO
YES
SiBE04-824
Replace the outdoor unit
PCB.
∗ Inverter checker
Part No.: 1225477
Correct the power supply or
replace the outdoor unit
PCB.
(R8256)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents