Input Over Current Detection - Daikin FVKS25BVMB Service Manual

Inverter pair floor standing type b-series
Hide thumbs Also See for FVKS25BVMB:
Table of Contents

Advertisement

SiBE06-514A
4.13

Input Over Current Detection

E8
Remote
Controller
Display
Method of
An input over-current is detected by checking the input current value with the compressor
running.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.07
Refer to P.121
Check No.08
Refer to P.121
Note:
If the model doesn't have SPM, replace the outdoor unit PCB.
Service Diagnosis
The following current with the compressor running continues for 2.5 seconds.
Cooling / Heating: Above 12A
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
∗ An input over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input over-current,
take the following procedure.
Get restarted and measure the
input current.
Input current flowing
above its stop level?
YES
Turn off the power and disconnect
the harnesses U, V and W.
Check with the inverter checker (∗).
Any LED off?
NO
Turn off the power, and reconnect
the harnesses. Turn on the power
again and get restarted.
Check No. 08
Check the discharge pressure.
Check No. 07
Check the installation condition.
NO
YES
Troubleshooting
Replace the outdoor unit
PCB.
∗ Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
(R4698)
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents