0016
40023
0017
40024
0018
40025
0019
40026
001A
40027
001B
40028
001C
40029
001D
40030
001E
40031
001F
40032
0020
40033
0021
40034
0022
40035
0023
40036
0024
40037
0025
40038
R/W:AABB
R/W
Read/write Channel 4 High alarm value
R/W:AABB
R/W
Read/write Channel 5 Low alarm value
R/W:AABB
R/W
Read/write Channel 5 High alarm value
R/W:AABB
R/W
Read/write Channel 6 Low alarm value
R/W:AABB
R/W
Read/write Channel 6 High alarm value
R/W:AABB
R/W
Read/write Channel 7 Low alarm value
R/W:AABB
R/W
Read/write Channel 7 High alarm value
R/W:AABB
R/W
Read/write masked AD-channels of the module
R/W:AABB
AA:00
BB:XXXXXXXX(Binary)
X: 1 Enable
R/W
Enable / Disable alarm status
R/W: xxxxxxxx (Binary)
X : 1 Enable X: 0 Disable
Least bit means the channel 0
R/W
Read/write SNMP Trap Number
R/W:AAAA
AAAA:0~4
0: close SNMP trap
R/W
(Read/Write)SNMP Trap IP1 Lo-Word
R: AABB(hex)
W: AABB(hex)
IP=X.X.AA.BB
R/W
(Read/Write)SNMP Trap IP1 Hi-Word
R: AAB
R/W
W: AABB(hex)
IP=AA.BB.X.X
R/W
(Read/Write)SNMP Trap IP2 Lo-Word
R: AABB(hex)
W: AABB(hex)
IP=X.X.AA.BB
R/W
(Read/Write)SNMP Trap IP2 Lo-Word
R: AABB(hex)
W: AABB(hex)
IP=X.X.AA.BB
R/W
(Read/Write)SNMP Trap IP3 Hi-Word
R: AABB(hex)
W: AABB(hex)
IP=AA.BB.X.X
R/W
(Read/Write)SNMP Trap IP3 Lo-Word
X:0 Disable
B(hex)
26