Korenix JetI/O 6510 User Manual page 27

Industrial intelligent ethernet i/o server
Hide thumbs Also See for JetI/O 6510:
Table of Contents

Advertisement

5.1.4
Exception Response
If an error occurs, the slave sends an exception response message to master consisting of
the slave address, function code, exception response code and error check field. In an
exception response, the slave sets the high-order bit (MSB) of the response function code
to one. The exception response codes are listed below.
Code
01
Illegal Function
02
Illegal Data Address
03
Illegal Data Value
04
Slave Device Failure
05
Acknowledge
06
Slave Device Busy
07
Negative Acknowledge
08
Memory Parity Error
5.2
JetI/O 6510 Modbus/TCP Address Mapping
JetI/O 6510 Common Register Map (Holding Registers)
Protocol
PLC
Address
Address
(Hex)
(Decimal)
0000
40001
0001
40002
0002
40003
0003
40004
Name
The message function received is not allowable
action.
The address referenced in the data field is not valid.
The value referenced at the addressed device
location is no within range.
An unrecoverable error occurred while the slave
was attempting to perform the requested action.
The slave has accepted the request and processing
it, but a long duration of time will be required to do
so.
The slave is engaged in processing a long-duration
program command.
The slave cannot perform the program function
received in the query.
The slave attempted to read extended memory, but
detected a parity error in the memory.
Access
R/W
R/W
R/W
R
Descriptions
Description
(Read/Write) Watch-dog enable/disable
R/W:AABB
AABB:0000H
(disable)
AABB:FF00H
(enable)
(Read/Write) Watch-dog cycle count
R/W:AABB
AABB:0001H~00FFH
(0.1*AABB)=Cycle Time (sec)
R:
Read the host-watchdog status
W:
Reset the host-watchdog status
R:AABB
AABB:0000H (remote module OK)
AABB:FF00H (host-watchdog fail)
W: AABB
AABB:FF00H(reset)
Read the firmware version
R:AAAA
AAAA:F12A (HEX)
24

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jeti/o 6500 seriesJeti/o 6550

Table of Contents