Suspending The Indoor Unit - Panasonic R410A Service Manual

R410a inverter
Table of Contents

Advertisement

Suspending the Indoor Unit

Depending on the ceiling type:
• Insert suspension bolts
or
• Use existing ceiling supports or construct a suitable
support.
Hole-in-anchor
Concrete
Hole-in-plug
Suspension bolt (M10 or 3/8")
(field supply)
WARNING
It is important that you use extreme care in supporting
the indoor unit inside the ceiling. Ensure that the ceiling
is strong enough to support the weight of the unit. Before
hanging the unit, test the strength of each attached
suspension bolt.
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts referring to the dimensional
data as shown in the figures on the previous page.
Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed,
lay the tubing into position for connection to the unit before
placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude
from the ceiling. (Cut the ceiling material, if necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field supply)
onto each of the 4 suspension bolts. Use 1 nut and 1
washer for the upper part, and 2 nuts and 1 washer for the
lower part, so that the unit will not fall off the suspension
lugs.
Insert
Ceiling tiles
Ceiling support
1-63
Nuts and washers
(use for upper and lower)
Double nuts
Suspension bolt
Hexagonal nut
Double nuts
● This shows an example of installation.
Air outlet duct
Suspension
bolt
Air-outlet grille
Indoor unit
Suspension bolt
Suspension lug
Notch
Bolt anchor
Ceiling material
1