3-2. Suspending the Indoor Unit

Depending on the ceiling type:
• Insert suspension bolts (Fig. 3-3)
or
• Use existing ceiling supports or construct a suitable
support (Fig. 3-4).
Hole-in-anchor
Hole-in-plug
Suspension bolt (3/8" or M10)
(field supply)
WARNING
It is important that you use extreme care in
supporting the indoor unit inside the ceiling. Ensure
that the ceiling is strong enough to support the
weight of the unit. Before hanging the unit, test the
strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine the pitch
of the suspension bolts referring to the dimensional data as
shown in Fig. 3-1 and Table 3-2.
Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay
the tubing into position for connection to the unit before
placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude
from the ceiling (Fig. 3-3). (Cut the ceiling material, if
necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field supply)
onto each of the 4 suspension bolts (Figs. 3-5 and 3-6). Use
1 nut and 1 washer for the upper part, and 2 nuts and 1
washer for the lower part, so that the unit will not fall off the
suspension lugs.
Concrete
Insert
Fig. 3-3
Ceiling tiles
Ceiling support
Fig. 3-4
Nuts and washers
(use for upper and lower)
Double nuts
Suspension bolt
Hexagonal nut
Double nuts
● This shows an example of installation.
Air outlet duct
Suspension
bolt
Air outlet grille
Indoor unit

3-3. Installing the Drain Pipe

(1) Prepare standard hard PVC pipe (O.D. 1-17/64" (O.D. 32
mm)) for the drain and use the supplied hose band to
prevent water leaks.
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to check
drainage. (Fig. 3-8)
CAUTION
● Do not use adhesive tape at the drain connection port on
the indoor unit.
● Insert the drain pipe until it contacts the socket, and
then secure it tightly with the hose band.
● Do not use the supplied drain hose bent at a 90° angle.
(The maximum permissible bend is 45°.)
8
Suspension bolt
Suspension lug
Notch
Fig. 3-5
Fig. 3-6
Bolt anchor
Air intake duct
Air intake grille
Ceiling material
Fig. 3-7