H01 Primary (Input) Overcurrent Detected - Panasonic R410A Service Manual

R410a inverter
Table of Contents

Advertisement

H01 Primary (input) overcurrent detected

1.
Error Detection Method
Primary current effective value detected overcurrent (trip current value).
Trip current value
Single-phase model
Heating
Cooling
2.
Error Diagnosis
1 Power
1-1
supply*
1-2
1-3
1-4
2
PC board
2-1
wiring
5
2-2
2-3
*
Check not only in the outdoor unit stop mode but in the drive mode.
A746894 : (U-60PE1R5, U-71PE1R5)
(for single-phase outdoor unit PCB)
A746845 : (U-125PE1R5, U-140PE1R5)
(for single-phase outdoor unit PCB)
2.5 hp
3 hp
4 hp
20.0A
20.0A
27.0A
18.5A
18.5A
27.0A
Not satisfied with + 10% rated supply voltage
Extreme voltage fluctuations
Extreme distortion of voltage waveform
Instantaneous blackout may sometimes occur.
Has FUSE 1/FUSE 2 blown?
Check the electrical conduction with tester.
Loose electrical wire connection
Replace CR board.
FUSE1
FUSE1
hp = horse power
Trip current value
5 hp
6 hp
3-phase model
29.0A
30.0A
Heating
29.0A
30.0A
Cooling
A746844 : (U-100PE1R5)
(for single-phase outdoor unit PCB)
A746967 : (U-100PE1R8, U-125PE1R8, U-140PE1R8)
(for 3-phase outdoor unit PCB)
5-32
hp = horse power
4 hp
5 hp
6 hp
12.5A
13.5A
14.5A
12.0A
12.6A
13.0A
Yes
Check power supply
No
1-2
Yes
Check power supply
No
1-3
Yes
Check power supply
No
1-4
Yes
Check power supply
No
2-1
2-3
Yes
No
2-2
Yes
Correct wiring
No
2-3
FUSE1
FUSE1