H01 Primary (input) overcurrent detected
1.
Error Detection Method
•
Primary current effective value detected overcurrent (trip current value).
Trip current value
Single-phase model
Heating
Cooling
2.
Error Diagnosis
1 Power
1-1
supply*
1-2
1-3
1-4
2
PC board
2-1
wiring
5
2-2
2-3
*
Check not only in the outdoor unit stop mode but in the drive mode.
A746894 : (U-60PE1R5, U-71PE1R5)
(for single-phase outdoor unit PCB)
A746845 : (U-125PE1R5, U-140PE1R5)
(for single-phase outdoor unit PCB)
2.5 hp
3 hp
4 hp
20.0A
20.0A
27.0A
18.5A
18.5A
27.0A
Not satisfied with + 10% rated supply voltage
Extreme voltage fluctuations
Extreme distortion of voltage waveform
Instantaneous blackout may sometimes occur.
Has FUSE 1/FUSE 2 blown?
Check the electrical conduction with tester.
Loose electrical wire connection
Replace CR board.
FUSE1
FUSE1
hp = horse power
Trip current value
5 hp
6 hp
3-phase model
29.0A
30.0A
Heating
29.0A
30.0A
Cooling
A746844 : (U-100PE1R5)
(for single-phase outdoor unit PCB)
A746967 : (U-100PE1R8, U-125PE1R8, U-140PE1R8)
(for 3-phase outdoor unit PCB)
5-32
hp = horse power
4 hp
5 hp
6 hp
12.5A
13.5A
14.5A
12.0A
12.6A
13.0A
Yes
Check power supply
No
1-2
Yes
Check power supply
No
1-3
Yes
Check power supply
No
1-4
Yes
Check power supply
No
2-1
2-3
Yes
No
2-2
Yes
Correct wiring
No
2-3
FUSE1
FUSE1