Samson 3730 Series Mounting And Operating Instructions page 48

Electropneumatic positioner
Table of Contents

Advertisement

Code list
Actuator does not move No supply air, mounting blocked.
E7
Recommended action Check supply air, positioner mounting and mA input signal.
Travel signal
E8
at lower limit
Recommended action Check positioner mounting and re-initialize the positioner.
E9
Travel signal
at upper limit
Recommended action Check positioner mounting and re-initialize the positioner.
E10 Not assigned
E11 Hardware
Recommended action Return positioner to SAMSON AG for repair.
E12 No factory calibration
Recommended action Return positioner to SAMSON AG for repair.
E13 Memory fault
Recommended action Return positioner to SAMSON AG for repair.
E14 Checksum error
data memory
Recommended action Return positioner to SAMSON AG for repair.
E15 Checksum error
calibration data
Recommended action Return positioner to SAMSON AG for repair.
48
EB 8384-1 EN
No input signal or input signal below 3.7 mA
Re-initialize the positioner.
Wrong pin position, wrong lever, wrong attachment direction when
NAMUR attachment is used.
Wrong pin position, wrong lever, wrong attachment direction when
NAMUR attachment is used.
Defective ceramic oscillator, positioner continues to run with an in-
ternal RC oscillator, but it should be replaced as soon as possible.
No factory calibration performed, memory defective.
Fault in the memory management
Data memory defective
Data memory defective

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730-1

Table of Contents