3.13.3 Parameters of the "Service level"

Name
Service level
P01
Control sequence
Mode selection by user via
P02
operating mode button
P04
Selection of °C or °F
P05
Sensor calibration
P06
Standard temperature display
P07
Additional user information
P08
Comfort basic setpoint
Minimum setpoint limitation in
P09
Comfort (Wmin
)
Comf
Maximum setpoint limitation
P10
in Comfort (Wmax
Comf
Setpoint of heating in Energy
P11
Saving
Setpoint of cooling in Energy
P12
Saving
Electrical heater in cooling
P13 *
mode
Button lock
(Press operating mode button
for 5 seconds to lock or
P14
unlock the buttons)
)
*
Parameter P13 and P54 is only displayed for application "2-pipe with electric
heater".
All temperature settings are in increments of 0.5 °C.
RDF302 Basic documentation
Factory setting
2-pipe : [0...3]
1 (Cooling only)
4-pipe: [2...4]
4 (Heating & Cooling)
1 (Comfort, Protection)
°C
0.0 °C
0 (Room temperature)
0 (no display)
21 °C
5 °C
)
35 °C
15 °C
30 °C
ON
0 (Disabled)
Range
0 = Heating only
1 = Cooling only
2 = Manual Heating or Cooling
3 = Auto Changeover
4 = Heating & cooling
1 = Comfort, Protection
2 = Comfort, Energy Saving,
Protection
0 = °C
1 = °F
- 3...3 °C
0 = Room temperature
1 = Setpoint
0 = No display
1 = Temperature in °C/°F
2 = Outside temperature
(via Modbus)
3 = Time of day (12 h, via Modbus)
4 = Time of day (24 h, via Modbus)
5...40 °C
5...40 °C
5...40 °C
OFF, 5 °C...Wcool
Eco
OFF, Wheat
...40 °C
Eco
OFF = disabled
ON = enabled
0 = Disabled
1 = Auto lock
2 = Manual lock
CE1P3079en