ON/OFF control
Control sequence
ON/OFF output
Modulating control: 3-position
Control sequence
modulating output
Note:
Setting the sequence and the control outputs
22 / 58
Siemens
Building Technologies
3.6.2

2-pipe fan coil unit

On 2-pipe applications, the thermostat controls a valve in heating / cooling mode
with changeover (automatically or manually), heating only, or cooling only. Cooling
only is factory-set (P01 = 1).
The diagrams below show the control sequence for 2-position control.
Heating mode
Y
YHC
1
w
0
½ SDH
½ SDH
T[°C] Room temperature
w
Room temperature setpoint
YHC Control command "Valve" or "Compressor"
The diagrams below show the control sequence for modulating PI control.
Heating mode
Y [%]
YHC
100
0
w
XpH
T[°C] Room temperature
w Room temperature setpoint
YHC
Control command "Valve"
The diagrams only show the PI thermostat's proportional part.
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
RDF302 Basic documentation
Cooling mode
Y
1
T[°C]
0
½ SDC
SDH
SDC
Cooling mode
Y [%]
100
T[°C]
0
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
YHC
w
½ SDC
Switching differential "Heating" (P30)
Switching differential "Cooling" (P31)
YHC
T[°C]
w
XpC
CE1P3079en
07 Dec 2011