Siemens RDF301 Instructions Manual

Siemens RDF301 Instructions Manual

Semi flush-mount communicating room thermostats
Hide thumbs Also See for RDF301:

Advertisement

s
RDF301, RDF600KN
CE1N3171en
2014-05-23
Semi flush-mount
communicating room
thermostats
For 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units
For use with compressors in DX type equipment
• KNX bus communications (S-mode and LTE mode)
• Backlit display
• 2P / PI / P control
• Outputs for on/off or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating/cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS or via local HMI
• Integration into Synco
• Integration into Desigo and Apogee via group addressing (ETS) or via
individual addressing
• Integration into third-party system via group addressing (ETS)
• AC 230 V operating voltage
RDF301.50
3
RDF301.50H
RDF301
RDF301.50..
RDF600KN
Building Technologies
171

Advertisement

loading

Summary of Contents for Siemens RDF301

  • Page 1 RDF301, RDF600KN RDF301.50 RDF301.50H Semi flush-mount RDF301 communicating room RDF301.50.. thermostats RDF600KN For 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units For use with compressors in DX type equipment • KNX bus communications (S-mode and LTE mode) • Backlit display •...
  • Page 2 • RDF600KN for round box, with min 60 mm diameter, min 40 mm depth and recessed rectangular box with 60.3 mm fixing centers • RDF301... for recessed rectangular box with 60.3 mm fixing centers Room temperature control (heating or cooling) in individual rooms and zones by means of: •...
  • Page 3 8-bit scene). RDF301.50H only: • Four buttons for Hotel applications to control via KNX S-mode. Same functions as RDF301.50, but with dedicated button labels for hotel applications: Make Up Room (MUR), Do Not Disturb (DND). Applications The thermostats support the following applications, which can be configured using the DIP-switches on the inner side of the thermostat's front panel or a commissio- ning tool.
  • Page 4 (B1) (B1) • 2-pipe fan coil unit • 4-pipe fan coil unit 3-position ON/OFF (heating or cooling) (heating and cooling) (B1) (B1) (B1) (B1) 4 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room thermostats 2014-05-23...
  • Page 5 (heating or cooling) heater (heating or cooling) ON/OFF • Chilled / heated ceiling • Chilled ceiling and radiator ON/OFF 3-position (heating or cooling) (heating and cooling) 5 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room thermostats 2014-05-23...
  • Page 6 B1 Return air temperature sensor or external valve actuator room temperature sensor (optional) Y2 Cooling valve actuator B2 Changeover sensor (optional) YE Electric heater M1 3- or 1-speed fan 6 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room thermostats 2014-05-23...
  • Page 7 Round CEE conduit box min 60 mm diameter and min 40 mm depth. MUR: Make Up Room, DND: Do Not Disturb. Ordering • When ordering, indicate both product number / SSN number and name: E.g. RDF301 / S55770-T104 room thermostat • Order valve actuators separately. Equipment combinations Data Type of unit Product no.
  • Page 8 Conduit box for semi-flush mounted ARG71 / N3009 thermostat RDF301... S55770-T137 KNX Power supply 160 mA (Siemens BT LV) 5WG1 125-1AB02 KNX Power supply 320 mA (Siemens BT LV) 5WG1 125-1AB12 KNX Power supply 640 mA (Siemens BT LV) 5WG1 125-1AB22...
  • Page 9 Fan speed Weekday 1…7 from KNX bus low, medium, high (1 = Monday / 7 = Sunday) 4 Heating/cooling mode Cooling Heating Electrical heater active 9 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room thermostats 2014-05-23...
  • Page 10 Mounting / Dismounting from a heating / cooling device, and not exposed to drips or splash water. • RDF301… : In case of limited space in the conduit box use the mounting bracket ARG70.3 to increase the headroom by 10mm •...
  • Page 11 RS232 KNX interface (e.g. Siemens N148 / UP146 / UP152) − OCI700 USB- KNX interface An external KNX bus power supply is required if an RDF301... / RDF600KN is Note connected directly to a tool (ACS or ETS) via KNX interface.
  • Page 12 Use ETS to assign the KNX group addresses of the RDF communication objects. Assign KNX group addresses Switching groups RDF301.50 and RDF301.50H have 2 switching groups with a pair of buttons each, RDF301.50… only which must be configured via ETS. The switching groups only work on S-mode. KNX serial number Each device has a unique KNX serial number inside the front panel.
  • Page 13 KNX bus Interface type KNX, TP1-64 (electrically isolated) Bus current RDF301 20 mA RDF600KN 5 mA Bus topology: See KNX manual (reference documentation, see below) Operational data Switching differential, adjustable...
  • Page 14 RAL 9003 white Weight without / with packaging RDF301.. 0.240 kg / 0.320 kg RDF600KN 0.150 kg / 0.220 kg *) The documents can be downloaded from http://siemens.com/bt/download. 14 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room thermostats...
  • Page 15 Installation Instruction: KNX Driver for PXC Modular; Document No. 565-132 Technical Spec Sheet: KNX Driver for PXC Modular; Document No. 127-1676 Technical Reference for KNX Driver; Document No. 140-0804 Application 6205 Point Map for RDF (RDF301 only) Connection terminals L, N...
  • Page 16 Connection diagrams Application Room thermostat 10 A RDF301... , RDF600KN 1- or 3-speed fan Valve actuator, 2- or 3-position CE+ CE- Y1, Y2 Valve actuator, 2-position Q1 Q2 Q3 Electric heater I II III C1, C2 1-stage compressor 2-pipe, 2-position...
  • Page 17 Dimensions Dimensions in mm RDF301... RDF600KN © 2009 - 2014 Siemens Switzerland Ltd Subject to change 17 / 17 Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en Building Technologies Semi flush-mount communicating room thermostats 2014-05-23...

This manual is also suitable for:

Rdf301.50 seriesRdf600knRdf301.50h