3.13.3 Parameters of the "Service level"

Name
Service level
P01
Control sequence
Mode selection by user via
P02
operating mode button
P04
Selection of ° C or ° F
Sensor calibration (build in
P05
sensor only)
P06
Standard temperature display
P07
Additional user information
P08
Comfort basic setpoint
Minimum setpoint limitation in
P09
Comfort (Wmin
)
Comf
Maximum setpoint limitation in
P10
Comfort (Wmax
)
Comf
Setpoint of heating in
P11
Economy (Wheat
)
Eco
Setpoint of cooling in
P12
Economy (Wcool
)
Eco
Electrical heater in cooling
P13 *
mode
Key lock
(Press operating mode button
for 5 seconds to lock or
P14
unlock the buttons)
)
*
Parameter P13 is only displayed for application "2-pipe with electric heater".
All temperature settings are in increments of 0.5 ° C.
RDF302 Basic documentation
Factory setting
Range
0 = Heating only
2-pipe: [0...3]
1 = Cooling only
1 (Cooling only)
2 = Manual Heating or Cooling
4-pipe: [2...4]
3 = Auto Changeover
4 (Heating & Cooling)
4 = Heating & cooling
1 = Comfort, Protection
2 = Comfort, Economy,
1 (Comfort, Protection)
0 = ° C
° C
1 = ° F
0.0 ° C
-3...3 ° C
0 = Room temperature
1 = Setpoint
0 (Room temperature)
2 = BUS temperature
0 = No display
1 = Temperature in ° C/° F
2 = Outside temperature (0...49 ° C)
3 = Time of day (12 h, via Modbus)
0 (No display)
4 = Time of day (24 h, via Modbus)
21 ° C
5...40 ° C
5 ° C
5...40 ° C
35 ° C
5...40 ° C
15 ° C
OFF, 5 °C...Wcool
30 ° C
OFF, Wheat
OFF = disabled
ON
ON = enabled
0 = Disabled
1 = Auto lock
0 (Disabled)
2 = Manual lock
Protection
(via Modbus)
Eco
...40 ° C
Eco
CE1P3079en
2022-06-17