Handling Faults - Siemens RDF302 Documentation

Semi-flush mount room thermostats with rs485 modbus communications
Hide thumbs Also See for RDF302:
Table of Contents

Advertisement

Enable electric heater
Fault information
X1 input, X2 input
X1 input, X2 input
Installation notes:
Temperature out
of range
Fault information
36 / 58
Siemens
Building Technologies
5
Enable electric
heater
6
Fault
7
Monitor input
(Digital)
8
Monitor input
(Temperature)
Operational action can be changed between normally open (NO) and normally
closed (NC) via parameter P39, P41
Each input X1 or X2 must be configured with a different function (1...5).
Exception: 1 or 2 inputs can be configured as fault (6) or monitor input (7,8)
X1 is factory-set to "Operating mode switchover" (3), X2 to "External sensor" (1)
If a multifunctional input is configured as analog: "Err" will be displayed when the
output is out of range (0...49 °C), open or shorted.
For more detailed information, refer to section 3.4 "Applications".
 For inputs X1 and X2, one physical switch can be used for up to 20 thermostats
(parallel connection).
 For sensors on inputs X1, X2, or D1, the cable length is max. 80 m.

3.10 Handling faults

When the room temperature is outside the measuring range, i.e. above 49 °C or
below 0 °C, the limiting temperatures blink, e.g. "0 °C" or "49 °C".
In addition, the heating output is activated if the current setpoint is not set to "OFF",
the thermostat is in heating mode and the temperature is below 0 °C.
For all other cases, no output is activated.
The thermostat resumes Comfort mode after the temperature returns to within the
measuring range.
For fault status messages on the Modbus, see section 3.11.1.
RDF302 Basic documentation
Digital input to enable / disable the electric
heater via remote control.
Enable electric heater is also possible via
Modbus. In this case, the function must not
be assigned to any local input X1, X2. See
also section 3.6.
Digital input to signal an external fault
(example: dirty air filter).
If the input is active, "ALx" is displayed and a
fault is sent on the Modbus. See also section
3.11.1.
(Alarm x, with x = 1 for X1, x = 2 for X2).
Note : Fault displays have no impact on the
thermostat's operation. They merely
represent a visual signal.
Digital input to monitor the state of an
external switch via Modbus.
Sensor input to monitor the state of an
external sensor (e.g. QAH11.1) via Modbus.
DI
DI
DI
AI
CE1P3079en
07 Dec 2011