Siemens RDF302 Documentation page 46

Semi-flush mount room thermostats with rs485 modbus communications
Hide thumbs Also See for RDF302:
Table of Contents

Advertisement

)
Notes: **
Parameters P36-37 and P50 will only appear when either X1 or X2 set to 2, the H/C changeover.
)
***
Parameters P35 and P44 will only appear when the application (DIP switch) set to 2 pipe 3 position.
)
***
Parameters d05 will only appear when the application (DIP switch) set to 2 pipe 3 position.
46 / 58
Siemens
Building Technologies
Name
Expert level
P61
Periodic fan kick Eco
P62
Service filter
P65
Protection heating setpoint
P66
Protection cooling setpoint
Baud Rate
P68
P69
Temporary Comfort setpoint
P70
Parity
P71
Restore factory setting
P81
Device address
Name
Diagnostics & test
d01
Application number
d02
X1 state
d03
X2 state
d05***
Test mode for checking the
Y11/Y21
This parameter can only be quit when
the setting is back at "---".
Press buttons + and – simultaneously
to escape.
actuator's running direction
RDF302 Basic documentation
Factory
Range
setting
OFF
0...359 min, OFF(360)
Off (0)
Off, 100...9900 h
8 °C
OFF, 5...WCoolProt;
WCoolProt = 40 °C max
OFF
OFF, WHeatProt... 40;
WHeatProt = 5°C min
2
0 = 4800 BPS
1 = 9600 BPS
2 = 19200 BPS
3 = 38400 BPS
OFF
OFF = Disabled
ON = Enabled
1
0 = Odd
1 = Even
2 = No parity
OFF
OFF = Disabled
ON = Reload start
"8888" is displayed for 3s during
reload process
1
1 ... 247
Range
NONE = (No application)
2P = 2-pipe
2P3P = 2-pipe 3-position
2PEH = 2-pipe with electric heater
4P = 4-pipe
0
= Not activated (for DI)
1
= Activated (DI)
0...49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
0
= Not activated (for DI)
1
= Activated (DI)
0...49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
"---" = no signal on outputs Y11 and Y21
OPE = output Y11 forced opening
CLO = output Y21 forced closing
CE1P3079en
07 Dec 2011