3.13.3 Parameters of the "Service level"

Name
Service level
Control sequence
Operation via room op selector
Unit
Measured value correction
Standard display
Additional display information
Comfort basic setpoint
Comfort setpoint minimum
Comfort setpoint maximum
Economy heating setpoint
Economy cooling setpoint
Electric heater when cooling
Button lock
Parameter display depends on selected application and function.
RDF301, RDF301.50 Basic documentation
Functions
Factory setting
2-pipe:
1 = Cooling only
4-pipe:
4 = Heating and Cooling
1
C (0)
0 K
0
0
21 °C
5 °C
35 °C
15 °C
30 °C
ON
0
Range
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
1 = Auto – Protection
2 = Auto - Comfort - Economy -
Protection
C = ° Celsius
F = ° Fahrenheit
– 3 ... 3 K
0 = Room temperature
1 = Setpoint
0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12h) (via bus)
4 = Time of day (24h) (via bus)
5 ... 40 °C
5 ... 40 °C
5 ... 40 °C
OFF, 5 ... WCoolEco;
WCoolEco = 40 °C max
OFF, WHeatEco ... 40 °C;
WHeatEco = 5C min
ON: Enabled
OFF: Disabled
0 = Unlocked
1 = Auto lock
2 = Manual lock
59 / 80
CE1P3171en
22 Jun 2010