Dimensional Data - Models Hd/Hdb - Modine Manufacturing HD Product & Performance Data

Gas-fired power vented unit heaters propeller & blower models
Hide thumbs Also See for HD:
Table of Contents

Advertisement

DiMENSiONAL DATA - MODEL HD/HDB
Propeller Units - Model HD
Figure 18.1
Dimensional Drawings - Model HD
-
MOUNTING HOLES TYP
3/8 X 1" LONG
Table 18.1 - Dimensions (inches) - HD
Models
A
B
C
D
E
F
G
H
Gas Connection
I
J
Fan Diameter
Approx. Shipping Weight (lbs.)
Vent Pipe Connector
Diameter (in)
Table 18.3 - Clearance to Combustibles, Model HD/HDB
Clearance To
Unit Side
Combustible Materials
Top and Bottom
Access Side
Non-Access Side
Rear
Vent Connector
18
G
C
J
I
ACCESS VIEW
HD30 HD45 HD60 HD75 HD100/125
26.8
26.8
26.8
26.8
12.2
12.2
18.0
18.0
16.5
16.5
16.5
16.5
14.9
14.9
14.9
14.9
10.1
10.1
15.9
15.9
7.5
7.5
10.7
10.7
18.5
18.5
18.5
18.5
7.6
7.6
7.8
7.8
1/2
1/2
1/2
1/2
34.5
34.5
34.5
34.5
22
22
25
25
10
10
14
14
55
60
80
85
3
3
3
3
Recommended
Service Clearance
1"
1"
1"
18"
1"
1"
18"
18"
4"
4"
Blower Units - Model HDB
Figure 18.2
Dimensional Drawings - Model HDB
-
MOUNTING HOLES TYP
3/8 X 1" LONG
ADJUSTABLE
LOUVERS
POWER VENTER
VENT PIPE CONNECTION
1.00
E
B
OPENING
D OPENING
Table 18.2 - Dimensions (inches) - HDB
Models
35.5
20.5
22.0
22.5
18.4
14.0
24.0
8.4
1/2
Gas Connection
43.0
31.0
18.0
Blower
125
Approx.Shipping Weight (lbs.)
Vent Pipe Connector
4
Diameter (in)
6-189.5
G
C
J
I
ACCESS VIEW
A
H
REAR VIEW
HDB 60 HDB 75 HDB100/125
A
26.8
26.8
B
18.0
18.0
C
16.5
16.5
D
14.9
14.9
E
15.9
15.9
F
10.7
10.7
G
18.5
18.5
H
7.8
7.8
1/2
1/2
I
34.5
34.5
J
25.0
25.0
9 - 7
9 - 7
92
97
3
ADJUSTABLE
LOUVERS
1.00
E
B
OPENING
MOUNTING
BRACKETS
ELECTRICAL
CONNECTIONS
GAS CONNECTION
ACCESS
PANEL
F
35.5
20.5
22.0
22.5
18.4
14.0
24.0
8.4
1/2
44.5
41.5
10 - 10
151
3
4

Advertisement

Table of Contents
loading