DiMENSiONAL DATA - MODEL PDP

Propeller Units - Model PDP
Figure 19.1 - Dimensional Drawings
Table 19.1 - Dimensions (inches) — PDP ➀
Dimension
Symbol
PDP 150 PDP 175 PDP 200 PDP 250 PDP 300 PDP 350 PDP 400
A
21
B
35-1/4
C
22
D
18-9/16
E
20
F
12
g
6-9/16
H
17-3/8
J ➁
5
K (Mounting
3/8-16
Holes) ➂
L ➃
35-13/16 35-9/16
M
29-13/16
W
X
AA
8
BB
7-1/4
CC
DD
2-3/4
EE
30-1/2
LL
31-1/8
gas Connections ➄
1/2
Fan Diameter
16
Approx. Weight
168
Do not use propeller units with duct work.
For some models, this is the dimension of the vent transition outlet supplied.
PDP 150 through PDP 300 — 2 holes (and the level hanging adjustment feature). PDP 350 through
PDP 400 — 4 holes. (Listed is the hole diameter and threads per inch to accept threaded rod).
Dimension equals overall plus 6".
For natural gas; may vary depending on control availability.
A
H
K
AA
E
BB
D (OPENING)
Model Number
23-1/2
25-5/8
25-5/8
35-1/4
40-1/4
40-1/4
22
25
25
21-1/16
23-3/16
23-3/16
20
24
24
12
13-1/2
13-1/2
6-9/16
7-1/2
7-1/2
19-7/8
22
22
5
5
6
3/8-16
3/8-16
3/8-16
40-3/4
40-3/4
29-9/16
34-3/4
34-3/4
8
9
9
7-1/4
7-1/4
7-1/4
2-3/4
3-3/8
3-3/8
30-1/2
32-7/8
32-7/8
31-1/8
34-7/8
34-7/8
1/2
1/2
1/2
18
20
20
175
239
239
M
C
F
CC
X
W
G
K
B
EE
L
(MIN. DISTANCE TO WALL)
28-5/8
33-5/8
40
40-1/4
40-1/4
40-1/4
25
25
25
26-3/16
31-3/16
37-1/2
24
24
24
14
7-1/2
7-1/2
7-1/2
25
30
36-3/8
6
6
6
3/8-16
3/8-16
3/8-16
40-3/4
40-3/4
44-3/16
34-3/4
34-11/16
38-3/16
5
5
16
16
9
9
9
7-1/4
7-1/4
7-1/4
3-3/8
3-3/8
6-13/16
32-7/8
32-7/8
32-7/8
36-1/4
35-1/2
40-1/2
1/2
3/4
3/4
22
22
24
269
338
418
6-189.5
DD
J
LL
Figure 19.2 - Combustible Material and
Service Clearances
C
Access
Side
D
Table 19.2 - Combustible Material
Clearances ➀
Access Non-Access
Model
Side
Side
Top Bottom
Size
(A)
(B)
(C)
150-175
1
1
4
200-400
1
1
5
➀ Provide sufficient room around the heater to allow for
proper combustion and operation of fan. Free area
around the heater must not be less than 1-1/2 times
the discharge area of the unit.