enphase Envoy Installation And Operation Manual page 55

Communications gateway
Table of Contents

Advertisement

Message Shown on
Events and Inventory
Screens
Bad Flash Image
Commanded Reset
Control Request
Critical Temperature
DC Power Too Low
DC Resistance Low -
Power Off
55
Description
Recommended Action: Contact Enphase Energy customer support.
Description: The microinverter is not producing power due to a software problem.
Recommended Action: No action is required; it will automatically resume normal
operation momentarily.
Description: The microinverter was reset, either following a successful software
download or by user command.
Recommended Action: No action is required.
Description: The Envoy has received a control request made via the Envoy
interface (Administration > Device Conditions and Controls page) or via Enlighten.
This uncommon condition will occur only during isolated troubleshooting
procedures by Enphase personnel.
Recommended Action: This condition should correct itself. No action is required.
Description: This rare condition occurs if the microinverter reports an internal
temperature that exceeds its rated range. It reacts by producing less power to
reduce internal temperature. This reflects internal temperature coming from a
sensor inside the microinverter, not the ambient temperature. Once the internal
temperature of the microinverter is once again within normal limits, it will resume
full power production and this event message will clear.
If the condition persists: Contact your installer or Enphase Energy customer
support at support@enphase.com.
Recommended Action: This condition should correct itself. No action is required.
Description: This condition may occur at sunrise or sunset, while the modules are
covered with snow, or during extreme weather. This event indicates that sunlight
levels are too low for effective production. Once sunlight levels increase, the
microinverter resumes power production and this event message will clear.
If the condition persists: Contact your installer or Enphase Energy customer
support at support@enphase.com.
Recommended Action: To clear this error using the Envoy interface, follow the
directions on page 49. The insulation resistance (IR) sensor can be reset via the
Enphase Envoy's Device Conditions and Controls page, or Enlighten's Current
Issues page. Note that the condition will not clear after sensor reset if the failure is
still present. If the condition persists, contact your installer or refer to the
Troubleshooting Guide at http://www.enphase.com/support.
Description: An IR sensor in the microinverter measures the resistance between
the positive and negative PV inputs to ground. If either resistance drops below a
threshold, the microinverter stops power production and raises this condition. This
may indicate defective module insulation, defective wiring or connectors, moisture
ingress, etc. Although the cause may be temporary, this microinverter condition
persists until the sensor is manually reset.
If the condition persists: If the event persists after clearing the condition from the
Envoy, contact your installer.
For further assistance, contact Enphase Energy customer support at
support@enphase.com.
 2014 Enphase Energy Inc.
Envoy Installation and Operation
141-00011 Rev 05