3.6 START-STOP OPERATION

HEAT
COOL
-20.0
SETPOINT
START-STOP MODE SELECTED
2. Verify that "START-STOP MODE SELECTED" is displayed on the MessageCenter and that the START-
STOP light is illuminated. The unit is now in Start-Stop operation.
Start-Stop is provided to reduce fuel or power consump-
tion. This feature allows full automatic control of the unit
shutdown and restart by monitoring refrigerated com-
partment temperature, battery charging amps and en-
gine coolant temperature (Engine Operation only). The
main function of Start-Stop Operation is to turn off the
refrigeration system near setpoint to provide an efficient
temperature control system and to initiate a restart se-
quence after certain conditions are met. The Start-Stop/
Continuous key is pressed to select between Continu-
ous Run and Start-Stop Operation. The corresponding
LED will be iluminated.
The microprocessor may be configured with Start-Stop
operation tied to the set point ranges for frozen and per-
ishable loads. The Start-Stop/Continuous key is locked
out if "START-STOP LOCKED" displays in the Messa-
geCenter when the key is pressed and the unit is in
Start-Stop Operation or "CONTINUOUS LOCKED" dis-
plays in the MessageCenter when the key is pressed
and the unit is in Continuous Run Operation. Refer to
Section 5.2.1 for Configuration information.
DEFROST
ALARM
+34.5 F
BOX TEMPERATURE
MANUAL
ALARM LIST
DEFROST
1. Press the START-STOP/CONTINUOUS key until the
START-STOP Light on the microprocessor illuminates.
START‐STOP
CONTINUOUS
SELECT
START‐STOP/
CONTINUOUS
If the unit fails to start after three start attempts, the A31
- "FAILED TO START-AUTO" alarm will be activated.
While running, if the unit shuts down, an internal counter
keeps track of the shutdowns. Should the unit shutdown
three consecutive times without running a minimum of
15 minutes between shutdowns, the A30 - "FAILED TO
RUN MINIMUM TIME" alarm will be activated. The shut-
down counter is cleared when the unit has run for 15 mi-
nutes.
In Standby Operation, the unit will stop for a
minimum of 5 minutes instead of 15 minutes.
Refer to Section 4.4 for more detailed information on
Start-Stop Operation.
3−9
START-STOP
LIGHT
NOTE