Electrical Alarms - Carrier VECTOR 6500 Operation & Service Manual

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

Alarm
Steps
NO.
71
BAD F2 OR F3 FUSE
TRIGGER–ON: One or more of the following fuse circuits have been open for more than 2
seconds: F2, F3
UNIT CONTROL:
RESET CONDITION: Alarm may be manually reset via keypad or by turning the unit off, then back on
again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). See Note 1 page 7−2. Operate the unit through the appropriate modes to see if any active alarm
occurs. Continue with the steps below as necessary.
1
Check Unit Operation
Did engine shutdown?
2
Check Fuses
a. Locate blown fuse(s).
b. Verify fuse size.
c. Inspect fuse & fuse holder.
3
Check Circuit
a. Check amperage draw on Speed
Relay circuit.
b. Check amperage draw on Run
Relay circuit.
62-11389
Alarm/Cause

7.7 ELECTRICAL ALARMS

Engine Operation: Alarm Only. If the engine shut off, see troubleshooting
steps below to correct.
Standby Operation: Additional verification required if the "NO A/C POWER"
configuration is set for "Installed and shutdown", the refrigeration system
will shutdown with the alarm on and PSCON still energized.
7−46
Corrective Action
Yes
Check F3.
No
Check F2.
Will have open circuit.
Refer to Section 2.13 for correct electrical values.
Must be correct rating for circuit. (See wiring
schematic. Section 10.)
Terminals tight; No signs of overheating, melting or
discoloration.
Refer to Section 2.13 for correct electrical values.