Page 1
Container Refrigeration OPERATION AND SERVICE 69NT40--551--500 TO 599 Container Refrigeration Units T--334 Rev B Downloaded from ManualsNet.com search engine...
Page 2
OPERATION AND SERVICE MANUAL CONTAINER REFRIGERATION UNIT Models 69NT40- -551- -500 to 599 Downloaded from ManualsNet.com search engine...
Page 3
TABLE OF CONTENTS PARAGRAPH NUMBER Page GENERAL SAFETY NOTICES ............Safety--1 FIRST AID .
TABLE OF CONTENTS - - Continued PARAGRAPH NUMBER Page 2.1.3 Evaporator Section ..............2--2 2.1.4 Compressor Section .
Page 5
TABLE OF CONTENTS - - Continued PARAGRAPH NUMBER Page 3.6.3 Sensor Configuration (dCF02) ............3--8 3.6.4 Logging Interval (dCF03) .
Page 6
TABLE OF CONTENTS - - Continued PARAGRAPH NUMBER Page TROUBLESHOOTING ............... . . 5- -1 UNIT WILL NOT START OR STARTS THEN STOPS .
Page 7
TABLE OF CONTENTS - - Continued PARAGRAPH NUMBER Page 6.12 EXPANSION VALVES ..............6--12 6.12.1 Checking Superheat .
Page 8
LIST OF ILLUSTRATIONS FIGURE NUMBER Page Figure 2--1 Refrigeration Unit - Front Section ........... . . 2--1 Figure 2--2 Evaporator Section .
Page 9
LIST OF ILLUSTRATIONS - - Continued FIGURE NUMBER Page Figure 6--22 Supply Sensor Positioning ............6--23 Figure 6--23 Return Sensor Positioning .
Page 10
SAFETY SUMMARY GENERAL SAFETY NOTICES SPECIFIC WARNING AND CAUTION STATEMENTS To help identify the label hazards on the unit and explain The following general safety notices supplement the level of awareness each one carries, an explanation specific warnings and cautions appearing elsewhere in is given with the appropriate consequences: this manual.
Page 11
WARNING WARNING With power OFF discharge the capacitor Make sure that the unit circuit breaker(s) before disconnecting the circuit wiring. (CB-1 & CB-2) and the START-STOP switch (ST) are in the “O” (OFF) position before connecting to any electrical power source. WARNING Do not use a nitrogen cylinder without a WARNING...
Page 12
(every 60 days) with corrosion inhibiting CRC 3-36a or 6-66 or LPS no. 2. CAUTION CAUTION Use only Carrier Transicold approved Polyol Ester Oil (POE) - EAL 32ST compres- sor oil with R-134a. Buy in quantities of one Recorder element capillary tubing may be quart or smaller.
Page 13
1.1 INTRODUCTION 1.3.2 Dehumidification The unit may be fitted with a humidity sensor. This The Carrier Transicold model 69NT40-551-500 to 599 sensor allows setting of a humidity set point in the series units are of lightweight aluminum frame controller. In dehumidification mode, the controller will construction, designed to fit in the front of a container operate to reduce internal container moisture level.
Page 14
1.3.12 Autotransformer 1.3.22 Upper Air (Fresh Air Make Up) The unit may be fitted with an upper fresh air makeup An autotransformer may be provided to allow operation assembly. The fresh air makeup assembly is available 190/230, 3-phase, 50/60 power. with a vent positioning sensor (VPS) and may also be autotransformer raises the supply voltage to the fitted with screens.
SECTION 2 DESCRIPTION 2.1 GENERAL DESCRIPTION 2.1.2 Fresh Air Makeup Vent 2.1.1 Refrigeration Unit - Front Section The function of the upper or lower makeup air vent is to The unit is designed so that the majority of the provide ventilation for commodities that require fresh air components are accessible from the front, see circulation.
2.1.3 Evaporator Section The evaporator fans circulate air through the container by pulling it in the top of the unit, directing it through the The evaporator section (Figure 2--2) contains the return evaporator coil, where it is heated or cooled, and temperature sensor, humidity sensor, thermostatic discharging it at the bottom.
2.1.4 Compressor Section The supply temperature sensor, supply recorder sensor and ambient sensor are located to the left of the compressor. The compressor section includes the compressor (with high pressure switch), a discharge pressure transducer Suction modulation valve is located behind the control and the suction pressure transducers.
2.1.5 Air-Cooled Condenser Section liquid injection valve, economizer expansion valve, and economizer solenoid valve. The air-cooled condenser section (Figure 2--4) consists of the condenser fan, condenser coil, receiver, sight The condenser fan pulls air through the bottom of the glass/moisture indicator, liquid line service valve, filter coil and discharges it horizontally through the drier, fusible plug, economizer, unloader solenoid valve, condenser fan grille.
2.1.6 Water-Cooled Condenser Section liquid injection valve (LIV), economizer expansion valve (EEV), economizer solenoid valve (ESV), and The water-cooled condenser section (Figure 2--5) moisture/liquid indicator. consists of a water-cooled condenser, sight glass, rupture disc, filter drier, water couplings, water pressure The water cooled condenser replaces the standard unit switch, economizer, unloader solenoid valve (USV), receiver.
2.1.7 Control Box Section 2.1.8 Communications Interface Module The control box (Figure 2--6) includes: the manual The communications interface module is a slave operation switches, circuit breaker (CB-1), compressor, module that allows communication with a master central fan and heater contactors, control power transformer, monitoring station.
2.2 REFRIGERATION SYSTEM DATA Model RSH105 Weight (Dry) 46.5 kg (103 lb) a. Compressor/Motor Approved Oil Mobil - 32ST Assembly Oil Charge 2957 ml (100 ounces) The oil level range, with the compressor off, Oil Sight Glass should be visible within the sight glass. Verify at -18C b.
2.3 ELECTRICAL DATA CB-1 Trips at 29 amps CB-2 (50 amp) Trips at 62.5 amps a. Circuit Breaker CB-2 (70 amp) Trips at 87.5 amps b. Compressor Full Load Amps (FLA) 13 amps @ 460 VAC Motor 380 VAC, Single Phase, 460 VAC, Single Phase, 50 Hz 60 Hz...
2.5 REFRIGERATION CIRCUIT 2.5.2 Economized Operation In the economized mode the frozen and pull down 2.5.1 Standard Operation capacity of the unit is increased by subcooling the liquid refrigerant entering the evaporator expansion valve. Starting at the compressor, (see Figure 2--7, upper Overall efficiency is increased because the gas leaving schematic) the suction gas is compressed to a higher the economizer enters the compressor at a higher...
SECTION 3 MICROPROCESSOR 3.1 TEMPERATURE CONTROL MICROPRO- operating parameters cargo temperature CESSOR SYSTEM parameters for future retrieval. Coverage of the temperature control software begins with paragraph 3.2. The temperature control Micro-Link 3 microprocessor Coverage of the DataCORDER software is provided in system (see Figure 3--1) consists of a key pad, display paragraph 3.6.
3.1.1 Key Pad NOTE The controlling probe in the perishable range The key pad (Figure 3--2) is mounted on the right-hand will be the SUPPLY air probe and the controlling side of the control box. The key pad consists of eleven probe in the frozen range will be the RETURN push button switches that act as the user’s interface with the controller.
3.2 CONTROLLER SOFTWARE The controller software is a custom designed program that is subdivided into configuration software and COOL HEAT DEFROST IN RANGE ALARM SUPPLY RETURN operational software. The controller software performs the following functions: a. Control supply or return air temperature to required limits, provide modulated refrigeration operation, economized operation, unloaded operation, electric SETPOINT/Code...
Figure 3- -4 Control Module The programming is divided into function codes. Some ice on the evaporator coil. In this way, defrosts are of the codes are read only while the remaining codes scheduled to occur only when necessary. may be user configured. The value of the user Once set point has been reached in frozen operation, configurable codes can be assigned in accordance with the automatic selection will set the time interval to...
However, pressure and current limit functions may 2. The unit is in the perishable steady state mode and restrict the valve if either exceeds the preset value. supply air temperature is less than 0.25C above set point. In perishable-pulldown mode, if return temperature is 3.
thermostat settings. (Refer to paragraph NO TAG.) The When temperature drops to set point minus 0.2C and temperature at which the defrost termination thermostat the compressor has run for at least five minutes, the unit will be considered “open” may be changed [in 0.1C will transition to the frozen idle mode.
Page 34
compressor on line. An example is alarm code “LO,” ty, economy, dehumidification and bulb (low main voltage), when a voltage drop of over 25% mode must be reactivated. occurs, an indication is given on the display, but the unit will continue to run. When an Alarm Occurs: a.
ISO Trip Header (When entered via Interrogation configuration to generic and selecting which data points program) to record may be done using the Carrier Transicold Data Economy Mode Start and End Retrieval Program. “Auto 1/Auto 2/Auto 3” Pre-Trip Start and End Bulb Mode Start 1.
3. Frequency 19. Suction pressure transducer 4. Humidity 20. Condenser pressure transducer 5. Phase A current 21. Vent position sensor (VPS) 6. Phase B current 3.6.4 Logging Interval (dCF03) 7. Phase C current 8. Main voltage The user may select four different time intervals 9.
Raw Data Report for ABC1234567 May 31, 2001 to Jun 04, 2001 System Configuration at the Time of Interrogation: Interrogated On Sept 05, 2001 Extracted by DataLINE Rev 1.0.0 Controller Software: 5120 Controller Serial #: 04163552 Bill of Lading #: 1 Origin: Origin Date: Destination:...
3.6.8 DataCORDER Power-Up a. DataReader The DataCORDER may be powered up in any one of The Carrier Transicold Data Reader (see Figure 3--6) is four ways: a simple to operate handheld device designed to extract 1. Normal AC power: The DataCORDER is powered data from the DataCORDER and upload it to a PC.
Exposing infested fruit to temperatures of 2.2C (36F) or below for specific periods results in the mortality of the DataReader various stages of this group of insects. In response to the demand to replace fumigation with this environmentally sound process, Carrier has integrated Cold Treatment capability into microprocessor system.
e. If no alarms are active, the Alarm Queue may be Place in pulp of the product located next Sensor 1 cleared. The exception to this rule is the DataCORD- to the return air intake. ER Alarm Queue Full alarm (AL91) , which does not Place in pulp of the product five feet have to be inactive in order to clear the alarm list.
Table 3- -4 Controller Configuration Variables (Sheet 1 of 2) CONFIGURATION TITLE DEFAULT OPTION NUMBER CnF01 Bypass Valve Enable CnF02 Evaporator Fan Speed dS (Dual) SS (Single) CnF03 Control Sensors FOUr duAL CnF04 Dehumidification Mode CnF05 Reserved for future use ----- CnF06 Condenser Fan Speed Select...
Page 42
Table 3- -4 Controller Configuration Variables (Sheet 2 of 2) CONFIGURATION TITLE DEFAULT OPTION NUMBER CnF41 Lower DTT Setting CnF42 Auto Pre-trip Start CnF47 Fresh Air Vent Position Sensor UPP,LOW,CUStOM CnF48 CFS Override CnF49 DataCORDER Configuration Restore CnF50 Enhanced Bulb Mode Selection Bulb, dEHUM CnF51 Timed Defrost Disable...
Table 3- -5 Controller Function Codes (Sheet 1 of 4) Code TITLE DESCRIPTION Note: If the function is not applicable, the display will read “-----” Display Only Functions Displays the SMV percent open. The right display reads 100% when the valve is Suction Modulation Cd01 fully open.
Page 44
Table 3- -5 Controller Function Codes (Sheet 2 of 4) Compressor Run This code displays the time remaining until the unit goes into defrost (in tenths of Time Remaining an hour). This value is based on the actual accumulated compressor running Cd25 Until Defrost time.
Page 45
Table 3- -5 Controller Function Codes (Sheet 3 of 4) The current limit is the maximum current draw allowed on any phase at any time. Limiting the unit’s current reduces the load on the main power supply. This is ac- Current Limit complished by reducing the SMV position until current draw is reduced to the set Cd32...
Page 46
Table 3- -5 Controller Function Codes (Sheet 4 of 4) Code Cd47 is used with optional economy mode. The values are 0.5C-4.0C. The Variable Economy Cd47 default is 3.0C. If the unit is not configured for economy mode, “----” will be dis- Temperature Setting played.
Table 3- -6 Controller Alarm Indications (Sheet 1 of 4) Code TITLE DESCRIPTION Alarm 05 is triggered if the controller detects continuous Manual Defrost Switch Manual Defrost AL05 action for 5 minutes or more. The alarm will only trigger off when the unit is pow- Switch Failure er cycled.
Page 48
Table 3- -6 Controller Alarm Indications (Sheet 2 of 4) Alarm 21 is triggered by one of the fuses (F1/F2) being opened on 18 VAC power supply to the controller. The suction modulation valve (SMV) will be opened and Micro Circuit Fuse AL21 Open (18 VAC) current limiting is halted.
Page 49
Table 3- -6 Controller Alarm Indications (Sheet 3 of 4) Alarm 53 is caused by the battery pack charge being too low to provide sufficient power for battery-backed recording. If this alarm occurs on start up, allow a unit AL53 Battery Pack Failure fitted with rechargeable batteries to operate for up to 24 hours to charge re- chargeable batteries sufficiently to deactivate the alarm.
Page 50
Table 3- -6 Controller Alarm Indications (Sheet 4 of 4) Suction Pressure AL66 Alarm 66 is triggered if a suction pressure transducer is out of range. Transducer Failure Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0% Humidity Sensor to 100% relative humidity.
Table 3- -7 Controller Pre-Trip Test Codes (Sheet 1 of 4) Code TITLE DESCRIPTION NOTE “Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu in- cludes P0, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1, P2, P3, P4, P5, P6, P7 and P8.
Page 52
Table 3- -7 Controller Pre-Trip Test Codes (Sheet 2 of 4) Setup: The High Speed Evaporator Fan is turned on, a current draw test is done after 60 seconds. High Speed P4-0 Evaporator Fan Pass/Fail Criteria: Passes if change in current draw is within the range speci- fied.
Page 53
Table 3- -7 Temperature Controller Pre-Trip Test Codes (Sheet 3 of 4) Suction Modulation Suction pressure is measured before and after the valve opens. If suction pres- P6-5 Valve Test sure does not increase, the test fails. Economizer Suction pressure is measured during Steps 4 and 5. If suction pressure does not P6-6 Valve Test increase, the test fails.
Page 54
Table 3- -7 Temperature Controller Pre-Trip Test Codes (Sheet 4 of 4) Requirements: Test P8-1 must pass for this test to execute. This test is skipped if the DataCORDER is not configured or not available. Setup: A 15 minute timer is started. The unit will be required to minimize control temperature error (supply temperature minus set point) until the timer expires.
Table 3- -8 DataCORDER Function Code Assignments NOTE Inapplicable Functions Display “-----” To Access: Press ALT. MODE key Code TITLE DESCRIPTION Recorder Supply Current reading of the supply recorder sensor. Temperature Recorder Return Current reading of the return recorder sensor. Temperature USDA 1,2,3 Temper- dC3-5...
Table 3- -9 DataCORDER Pre-Trip Result Records Test TITLE DATA Heater On Pass/Fail/Skip Result, Change in current for Phase A, B and C Heater Off Pass/Fail/Skip Result, Change in currents for Phase A, B and C Pass/Fail/Skip Result, Water pressure switch (WPS) - Open/Closed, Condenser Fan On Change in currents for Phase A, B and C Condenser Fan Off...
Table 3- -10 DataCORDER Alarm Indications To Access: Press ALT. MODE key Code No. TITLE DESCRIPTION The supply recorder sensor reading is outside of the range of -50C to 70C (-58F to +158F), or the probe check logic has determined there is a fault Recorder Supply with this sensor.
SECTION 4 OPERATION 4.1 INSPECTION (Before Starting) 2. Plug the 460 VAC (yellow) cable into a de-energized 380/460 VAC, 3-phase power source. Energize the power source. Place circuit breaker (CB-1) in position WARNING “I” (ON). Close and secure control box door. 4.2.2 Connection To 190/230 VAC Power Beware of unannounced starting of the An autotransformer (Figure 4--1) is required to allow...
4.3.1 Upper Fresh Air Makeup Vent b. Reduced Flow for Fresh Air Makeup On some models the air slide is supplied with two Two slots and a stop are designed into the disc for air adjustable air control disks. The fresh air makeup can be flow adjustments.
4.4 CONNECT WATER-COOLED CONDENSER 4.6 STARTING AND STOPPING INSTRUCTIONS The water-cooled condenser is used when cooling WARNING water is available and heating the surrounding air is objectionable, such as in a ship’s hold. If water-cooled operation is desired, connect in accordance with the Make sure that the unit circuit breaker(s) following subparagraphs.
4.7.4 Complete Inspection 3. Pre-trip also initiated communications. The operation is the Allow unit to run for five minutes to stabilize conditions same as for the key pad initiation described and perform a pre-trip diagnosis in accordance with the below except that should a test fail, the following paragraph.
ing the PRE-TRIP key. The unit will then resume nor- If the probe check option is configured for special, the mal operation. If the user decides to terminate a test above criteria are applicable. A defrost with probe check but remain at the test selection menu, the user may will be initiated if 25 of 30 readings or 10 consecutive press the UP ARROW key.
RISING FALLING PULL DOWN TEMPERATURE TEMPERATURE +2.5C +2.5C (4.5F) (4.5F) START UNLOADED, MODULATED MODULATED TRANSITION TO COOLING COOLING ECONOMIZED UNLOADED UNLOADED OPERATION +.20C +.20C SET POINT SET POINT AIR CIRCULATION UNLOADED OPERATION -0.20C -0.20C AIR CIRCULATION AIR CIRCULATION -0.5C -0.5C (0.9F) (0.9F) HEATING...
4.10.2 Sequence of Operation - Perishable Mode f. If the calculation determines cooling is no longer re- Cooling quired, contacts TC and TN are opened to de-ener- gize compressor motor and condenser fan motor. NOTE The cool light is also de-energized. In the Conventional Perishable Mode of Opera- g.
4.10.4 Sequence of Operation - Frozen Mode Cool- 4.10.5 Sequence of Operation - Defrost The defrost cycle may consist of up to three distinct operations. The first is de-icing of the coil, the second is a. With supply air temperature above set point and de- a probe check cycle and the third is snap freeze.
Defrost may be initiated any time the defrost If controller function code CnF33 is configured to snap temperature sensor reading falls below the controller freeze, the controller will sequence to this operation. defrost termination thermostat set point. Defrost will The snap freeze consists of running the compressor terminate when the defrost temperature sensor reading without the evaporator fans in operation for a period of rises above the defrost termination thermostat set point.
SECTION 5 TROUBLESHOOTING REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.1 UNIT WILL NOT START OR STARTS THEN STOPS External power source OFF Turn on Start-Stop switch OFF or defective Check No power to unit Circuit breaker tripped or OFF Check Autotransformer not connected 4.2.2 Circuit breaker OFF or defective...
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING Abnormal pressures Abnormal temperatures 5.15 Abnormal currents 5.16 Controller malfunction Evaporator fan or motor defective 6.15 Shortage of refrigerant 6.3 /6.4 Refrigeration system Suction modulation valve lost track of step count Power cycle Suction modulation valve malfunction 6.18...
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.6 UNIT WILL NOT DEFROST PROPERLY - Continued Manual defrost switch defective Replace Will not initiate defrost manually Defrost temperature sensor open 4.10.5 Initiates but relay (DR) drops Low line voltage Heater contactor or coil defective Replace Initiates but does not defrost Heater(s) burned out...
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.9 CONTROLLER MALFUNCTION Defective sensor 6.22 Defective wiring Check Will not control Stepper motor suction modulation valve circuit malfunction 6.18 Low refrigerant charge 6.3 /6.4 5.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW Frost on coil Evaporator coil blocked Dirty coil...
REMEDY/ CONDITION POSSIBLE CAUSE REFERENCE SECTION 5.14 COMPRESSOR OPERATING IN REVERSE NOTE It is normal for the compressor to run in reverse for 15 seconds when the compressor has been off for 6 hours or more. CAUTION Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal compressor damage.
Pressurized mixtures of air models covered within this manual. The manifold or gases containing oxygen can lead to ex- gauge/hose set is available from Carrier Transicold. plosion. (Carrier Transicold part number 07-00294-00, which includes items 1 through 6, Figure 6--2.) To perform service using the manifold gage/hose set, do the 6.1 SECTION LAYOUT...
3. Evacuate to 10 inches of vacuum and then charge CAUTION with R-134a to a slightly positive pressure of 0.1 kg/ (1.0 psig). To prevent trapping liquid refrigerant in the 4. Front seat both manifold gauge set valves and dis- manifold gauge set be sure set is brought to connect from cylinder.
(see gauge. (The pump is available from Carrier Trans- Figure 6--4). Be sure the service hoses are suited for icold, part number 07-00176-11.) evacuation purposes.
c. The area between the suction modulating valve and a. Connect the gauge manifold to the compressor dis- evaporator expansion valve may not be open to the charge and suction service valves. For units operat- access valves. To ensure evacuation of this area, ing on a water cooled condenser, change over to air check that the suction modulating valve is more than cooled operation.
6.4 REFRIGERATION SYSTEM SERVICE - UNITS WITH SEMI-HERMETIC PIPING (without Ser- vice Valves) 6.4.1 Service Connections The compressor is fitted with access valves at the suction connection, economizer fitting and liquid line fitting to enable servicing of the system. Refrigerant must be removed from system before performing service.
Page 77
In the U.S.A., refer to EPA Sec- displacement) and an electronic vacuum gauge. (The tion 608. pump is available from Carrier Transicold, part number 07-00176-11.) a. Connect the gauge manifold to the liquid and suction access valves. For units operating on a water cooled Additional time may be saved during a complete system condenser, change over to air cooled operation.
6.4.7 Adding Refrigerant to System (Partial e. Remove and discard the rubber gasket that was lo- Charge) cated between the terminal box and the compressor shell. a. Examine the unit refrigerant system for any evidence f. Remove the rotalock fittings from the suction, dis- of leaks.
j. The replacement compressor is shipped with an oil p. Place the new Teflon seals (kit items #2 and 3) at the charge of 591ml (20 ounces). Before sliding the new compressor service ports and connect the four ser- compressor in the unit, remove the cap from the oil vice fittings loosely.
Install a new high pressure switch after verifying CAUTION switch settings. d. Evacuate, dehydrate and recharge. Use only Carrier Transicold approved e. Start unit, verify refrigeration charge and oil level. Polyol Ester Oil (POE) - Mobil 32ST com- pressor oil with R-134a. Buy in quantities of 6.7.2 Checking High Pressure Switch...
6.8 CONDENSER COIL (0.08” +/- 0.03”) from the outside of the orifice open- ing. Spin fan by hand to check clearance. The condenser consists of a series of parallel copper g. Close and secure condenser fan screen guard. tubes expanded into copper fins. The condenser coil must be cleaned with fresh water or steam so the air flow 6.10 WATER- -COOLED CONDENSER CLEANING is not restricted.
Summary of Procedure: a. Drain water from condenser tubing circuit. Clean water tubes with Oakite No. 22 to remove mud and slime. b. Flush. c. De-scale water tubes with Oakite No. 32 to remove scale. d. Flush. e. Neutralize. f. Flush. g.
NOTE 2. Check the moisture-liquid indicator if the indicator shows a high level of moisture, the filter drier should If the condenser cooling water is not being used be replaced. as drinking water or is not re-circulated in a b. To Replace Filter Drier closed or tower system, neutralizing is not nec- essary.
c. Connect an accurate gauge to the service port direct- ly upstream of the suction modulating valve d. Set the temperature set point to -18C (0F), and run unit until conditions stabilize. Partially block the con- denser airflow with cardboard or similar material and raise the discharge pressure to above 175 psig (12 bar).
1. Copper Tube 2. Bi-metallic Tube 3. Braze Rod 4. Use of a wet cloth is (Apply heat for 10-15 sec- Connection (Apply heat for (’Sil-Phos” = 5.5% Silver, not necessary due to rapid onds) 2-5 seconds) 6% Phosphorus) heat dissipation of the bi-metallic connections Figure 6- -14 Hermetic Thermostatic Expansion Valve Brazing Procedure f.
6.15.1 Replacing The Evaporator Fan Assembly WARNING Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply before working on moving parts. a. Remove upper access panel (see Figure 2--2) by removing mounting bolts and TIR locking device. Reach inside of unit and remove the Ty-Rap securing the wire harness loop.
6.15.3 Assemble The Evaporator Fan Assembly 6.16.2 Removing The Capacitor a. Assemble the motor and plastic spacer onto the stator. WARNING Make sure power to the unit is OFF and NOTE power plug disconnected before removing When removing the black nylon evaporator fan capacitor(s).
take place immediately. If the timer is not active, Press the ENTER key and SELCt will appear in the changes will not take place for a few seconds after the left display. timer is started. When the timer times out, override c.
6.18 SUCTION MODULATION VALVE The SMA-12 portable stepper drive tester (Carrier Transicold part number 07-00375-00) is a battery On start up of the unit, the valve will reset to a known operated stepper drive which will open and close the open position.
TP 9 requires handling and removal of a module. a. Obtain a grounding wrist strap (Carrier Transicold This test point is the chassis (unit frame) ground part number 07-00304-00) and a static dissipation connection.
6.20.3 Controller Programming Procedure b. Procedure for loading Configuration Software: 1. Turn unit OFF using start-stop switch (ST). To load new software into the module, the programming card is inserted into the programming/software port. 2. Insert software/programming PCMCIA card contain- ing the following (example) files into the program- ming/software port.
6.22 TEMPERATURE SENSOR SERVICE tions 14, 13, 11. Procedures for service of the Return Recorder, Return d. Using Driver Bit, Carrier Transicold part number Temperature, Supply Recorder, Supply Temperature, 07--00418--00, remove the 4 screws securing the dis- Ambient, Defrost Temperature, Compressor Discharge play module to the control box.
CAUTION Do not allow moisture to enter wire splice area as this may affect the sensor resis- tance. m. Position sensor in unit as shown in Figure 6--22 and re-check sensor resistance. n. Reinstall sensor, refer to paragraph 6.22.3. NOTE The P5 Pre-Trip test must be run to inactivate 1.
Page 95
a. Turn power to the unit OFF. NOTE Failure to press the change chart button, when b. Open the recorder door (item 1, see Figure 6--24). changing a chart with the power OFF, may result in the chart advancing when power is c.
Connector Recorder Door Calibration Button Change Chart (Located underneath) Button Mounting Screws, Recorder Box #10-24 x 7/16 inches long Pen Tip Hold Down Tab Stylus Arm Chart Retaining Nut Figure 6- -24 Electronic Partlow Temperature Recorder 6.23.3 Adjusting the Recorder Stylus NOTE Use chart CTD part number 09-00128-00 (F) Proper stylus force upon the chart paper is important.
An adhesive sealant must be used to make the repair watertight. The adhesive sealant c. Press the calibration button and the pen will position (Sikaflex 221) is included in Crack Repair Kit Carrier itself to the correct temperature reading. Transicold...
Static Mixing Tube (Loctite 983440) 07-00390-00 . . . Instruction Sheet 98-02338-00 Note: Insert repair procedures require use of an Application Gun, Carrier part number 07-00391-00 (Loctite 983435) Table 6- -6 Drill Information Item Insert part number Drill size and depth 34- 06231- 01 10.3 mm x 17.8 mm deep (0.404 in.
Units that have been factory provisioned for installation 5.2 in-lbs of a communication interface module (CIM) have the 9.6 in-lbs required wiring installed. If the unit is not factory 20 in-lbs provisioned, a provision wiring kit (Carrier Transicold 23 in-lbs 75 in-lbs part number 76-00685-00) must installed.
SECTION 7 ELECTRICAL WIRING SCHEMATICS 7.1 INTRODUCTION This section contains the Electrical Schematics and Wiring Diagrams. The diagrams are presented as follows: Figure 7--1 provides the legend for use with Figure 7--2, the schematic diagram for units with single--phase motor, normal evaporator fan capability, and Figure 7--3, the schematic diagram for units with single--phase motor, single evaporator fan capability.
FOR VPS, see Figure 7- -8 Figure 7- -2 SCHEMATIC DIAGRAM - Single Phase, Normal Evaporator Fan Capability T-334 7--3 Downloaded from ManualsNet.com search engine...
SEE FIGURE SEE FIGURE TransFRESH CONTROLLER Main Power From QC1 From KA2 From ECG1 From ECJ1 CONTROLLER LEGEND Emergency Bypass BYPASS MODULE EMERGENCY BYPASS FUSE-EMERGENCY BYPASS FUSE-TransFRESH MANUAL SWITCH SUCTION MODULATING VALVE Figure 7- -6 SCHEMATIC DIAGRAM-TransFRESH and Emergency Bypass (For Single Phase Evaporator Fan Motor Applications) T-334 7--7...
LOWER VENT POSITION SENSOR UPPER VENT POSITION SENSOR (SEE NOTE) (SEE NOTE) (SEE NOTE) NOTE: VPS2 TO M1 FOR STANDARD VPS. VPS2 TO T1 FOR UPPER VPS VIEWABLE WHILE UNIT IS ON BATTERY POWER. Figure 7- -8 SCHEMATIC AND WIRING DIAGRAM - Upper and Lower Vent Position Sensors T-334 7--9 Downloaded from...
Figure 7-5 for detail Control Box Location Condenser Location Figure 7-5 for detail Figure 7- -9 WIRING DIAGRAM - Single Phase, Normal Evaporator Fan Capability (Sheet 1 of 2) T-334 7--10 Downloaded from ManualsNet.com search engine...
Page 112
Figure 7- -9 WIRING DIAGRAM - Single Phase, Normal Evaporator Fan Capability (Sheet 2 of 2) T-334 7--11 Downloaded from ManualsNet.com search engine...
Figure 7-5 for detail Control Box Location Condenser Location Figure 7-5 for detail Figure 7- -10 WIRING DIAGRAM - Normal Evaporator Fan Capability with Bypass Module (Sheet 1 of 2) T-334 7--12 Downloaded from ManualsNet.com search engine...
Page 114
Figure 7- -10 WIRING DIAGRAM - Normal Evaporator Fan Capability with Bypass Module (Sheet 2 of 2) T-334 7--13 Downloaded from ManualsNet.com search engine...
Figure 7- -11 WIRING DIAGRAM - Single Phase, Single Evaporator Fan Capability (Sheet 1 of 2) T-334 7--14 Downloaded from ManualsNet.com search engine...
Page 116
Figure 7- -11 WIRING DIAGRAM - Single Phase, Single Evaporator Fan Capability (Sheet 2 of 2) T-334 7--15 Downloaded from ManualsNet.com search engine...