Carrier VECTOR 6500 Operation & Service Manual page 175

Single-temp trailer and rail refrigeration units with advancet microprocessor
Table of Contents

Advertisement

Alarm
Steps
NO.
58
CHECK REMOTE SWITCH 2 (REMS2)
TRIGGER–ON: Remote Switch 2 is set to activate an alarm if the switch is activated (opened or
closed, depending on switch type) for more than five seconds.
UNIT CONTROL: May be configured as alarm only, alarm and force low engine speed or alarm and
shutdown.
RESET CONDITION:
Alarm Only: Auto Reset after the switch has de-activated for more than five seconds.
Shutdown: Auto Reset after three minutes (minimum off time for door open condition) and the switch
has de-activated for more than five seconds.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Determine what REMS2 is controlled by.
REMS2 may be connected to a com-
partment door or some other device
and used to remotely control the
compartment.
2
Check To See If REMS2 Has Activated
Inspect device used to activate
REMS2.
3
Check "REMS2 (Remote Switch 2) Configuration
Verify that Configuration is set for the
type of switch being used (i.e. when
switch is activated, switch contacts
are closed; etc.)
4
Check Wiring
a. Visually inspect wiring to Remote
Switch #2.
b. Visually inspect condition of switch Must not be damaged, wet, corroded, etc.
c. Check circuit. (See wiring schemat-
ic Section 10.)
5
Temporary Solution Tip
In the event of a defective switch
that can not be repaired or replaced,
and the switch is forcing the unit into
a shutdown, this alarm may be tem-
porarily overridden by setting the
correct Functional Parameter.
Locate and inspect 10 position con-
nector for optional sensors and
switches (REMSN, see wiring sche-
matic Section 10).
62-11389
ALARM / CAUSE
IF A SWITCH IS INSTALLED
IF A SWITCH IS NOT INSTALLED
CORRECTIVE ACTION
Locate the device used as REMS2.
For example, compartment door must be closed, and
switch must be de-activated.
Configuration must agree with switch type. Refer to
"REMS2 (Remote Switch 2)" Configuration,
Table 5−2.
Wiring must be connected.
With the switch contacts closed, check for voltage
from microprocessor terminal 2MP13, through the
wiring and switch to ground.
In the Functional Parameter list set OVERRIDE
REMS2 SHUTDOWN to YES.
Connector must have cap on,
No corrosion or moisture inside connector.
If there is a problem with the connector and there are
no remote sensors or switches in the unit, the con-
nector may be removed and each individual wire sep-
arated from the others, terminated and insulated with
heat shrink.
7−42