Special Control - Daikin RQYQ140-180PY1 Service Manual

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

SiBE341001
2.7

Special Control

2.7.1 Pump-down Residual Operation
If the liquid refrigerant stays in the evaporator at the startup of a compressor, this liquid refrigerant enters the
compressor, thus resulting in diluted oil in the compressor and then degraded lubrication performance.
Consequently, in order to recover the refrigerant in the evaporator while the compressor stops, the pump-down residual
operation is conducted.
Electric
Part Name
Symbol
Compressor
M1C
Outdoor unit fan
M1F
Electronic expansion
Y1E
valve (Main)
Electronic expansion
valve (Refrigerant
Y2E
charge)
Electronic expansion
Y3E
valve (Subcooling)
Solenoid valve
(Refrigerant regulator
Y1S
hot gas)
Solenoid valve
(Refrigerant regulator
Y2S
liquid pipe)
Solenoid valve
(Refrigerant regulator
Y3S
gas vent pipe)
Solenoid valve (Hot
Y4S
gas)
Solenoid valve
Y5S
(Circuit of oil return)
Four way valve (Heat
Y6S
exchanger switch)
Four way valve (Dual
Y7S
pressure gas pipe)
Four way valve
Y8S
(Mixing unit)
Solenoid valve
Y9S
(Mixing unit inlet)
Ending condition
Function
Normal Cooling
Master Unit
Slave Unit
124 Hz
Fan control
Fan control
480 pls
0 pls
0 pls
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• 5 min. passed
• Pe_min<0.49MPa
• Pc_max>2.94MPa
OR
• Master unit Tdi > 110°C
• Master unit Tp > 125°C
Normal Simultaneous Cooling / Heating
Master Unit
OFF
124 Hz
Fan control
Four way valve "ON":
0 pls
0 pls
Four way valve
"OFF": 480 pls
0 pls
0 pls
0 pls
0 pls
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OR
Detailed Control Functions
Slave Unit
OFF
Fan control
Four way valve "ON":
0 pls
Four way valve
"OFF": 480 pls
0 pls
0 pls
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• 3 min. passed
• Pe_min<0.25MPa
• Pc_max>3.13MPa
• Master unit Tdi > 110°C
• Master unit Tp > 140°C
52