Troubleshooting by Remote Controller
F9
2.15 "
" Outdoor Unit : Malfunction of BS Unit Electronic
Expansion Valve
F9
Remote
Controller
Display
Applicable
BSVQ100-250PV1
RQCE-PY1
Models
Method of
This malfunction is detected by whether or not all coils of the electronic expansion valve have
continuity.
Malfunction
Detection
Malfunction
When the power supply turns ON, there is no currents pass through the common (COM[+]).
Decision
Conditions
Supposed
Causes
127
Connector disconnected from the electronic expansion valve
Faulty of the electronic expansion valve coil
Faulty PCB of the BS unit
SiBE341001
Troubleshooting