Daikin RQYQ140-180PY1 Service Manual page 167

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

SiBE341001
Troubleshooting
Remove and insert the
connectors shown below.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the condition of the
power supply.
Check if power supply
voltage is 380 to 415V.
Check if there is open
phase or faulty wiring.
Check if power supply
voltage side unbalance is
with in 6V.
There are
problems on the
condition of power supply
described
above.
NO
The
insulation resistance
of compressor is not
more 100kΩ.
NO
The
insulation resistance
of fan motor is not
more 1MΩ.
NO
CHECK 4
Is the power transistor
normal?
YES
X4A (A3P) ↔ X20A (A1P)
X6A (A3P) ↔ X28A (A1P)
Has the
inverter PCB caused
damage?
NO
A
YES
YES
YES
NO
YES
Troubleshooting by Remote Controller
Correct the fault.
Replace the compressor.
Replace the fan motor.
If the fan motor is badly
damaged, replace the
inverter PCB (A4P).
Replace the inverter PCB (A3P).
Replace the inverter PCB (A3P).
If the inverter PCB is badly
damaged, compressor and
fan motor are likely to get
faulty.