SiBE341001
U4
2.33 "
" Malfunction of Transmission between Indoor Units

and Outdoor Units

U4
Remote
Controller
Display
Applicable
All indoor unit models
RQYQ-PY1
Models
RQEQ-PY1
Method of
Check if the transmission between indoor unit and outdoor unit is correctly executed using
micro-computer.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
Troubleshooting
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defect of outdoor unit main PCB (A1P)
Defect of indoor unit PCB
Troubleshooting by Remote Controller