Field Setting from Outdoor Unit
a. "Setting mode 1"
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group
• COOL/HEAT selection (SLAVE)················Used to select COOL or HEAT by outdoor unit group
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Normally, "Setting mode 1" is set. In
case of other status, push MODE
(BS1) button one time and set to
"Setting mode 1".
Push the SET (BS2) button to set
the blinking of LED to any of
conditions shown on the right.
Push the RETURN (BS3) button to
determine the setting.
Procedure for checking check items
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pushing the RETURN (BS3) button
will bring the system to the initial
state of "Setting mode 1".
73
Setting (displaying) item
For selection by individual outdoor unit (factory set)
For selection in a batch of outdoor unit group with master unit
For selection in a batch of outdoor unit group with slave unit
Pushing the RETURN (BS3) button will return the system to the initial condition of
"Setting mode 1".
MODE
TEST
H1P
H2P
h
h
(V2763)
unit (factory set).
with the master unit.
with the slave unit.
MODE
TEST
H1P
H2P
h
h
h
h
h
h
COOL/HEAT select
Low
IND
MASTER
SLAVE
noise
H3P
H4P
H5P
H6P
k
h
h
h
COOL/HEAT select
noise
IND
MASTER
SLAVE
H6P
H3P
H4P
H5P
l
h
h
h
l
h
h
h
l
Demand
H7P
h
Current operating conditions
hNormal kAbnormal
lIn preparation or in check
operation
Setting of COOL/HEAT selection
khhBy individual outdoor unit
hkhIn a batch of outdoor unit
group with master unit
hhkIn a batch of outdoor unit
group with slave unit
Low noise operating conditions
hIn normal operation
kIn low noise operation
Demand operating conditions
hIn normal operation
kIn demand operation
Test Operation
SiBE341001
k ON
h OFF
l Blink
Low
Demand
H7P
h
h
h
h
h
h