Daikin RQYQ140-180PY1 Service Manual page 176

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Troubleshooting
167
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Diagnosis Flow 1
Confirmation of malfunction 3 Confirmation of malfunction 4
Check if any disconnection
or connection error is
detected in connecting
wires with external control
adaptor.
YES
Check if the normal
condition monitor LED
for the outdoor unit
PCB blinks.
YES
Check if the normal
condition monitor LED
for the external control
adaptor blinks.
YES
NO
NO
Check if power is
supplied to the
outdoor units.
YES
Check if the power
NO
supply wire for the
external control adaptor
is connected to 5V
supply line.
YES
SiBE341001
Correct the connecting wiring
with the external control
adaptor.
NO
Supply power to the outdoor
unit.
Replace the outdoor unit main
PCB.
NO
Connect the power supply wire
for the external control adaptor
to 5V supply line.
Replace the PCB of the external
control adaptor.
Replace the outdoor unit main
PCB.