When the equivalent pipe length between outdoor unit multi connection piping kit and indoor units is 90m or more, the size of main pipes (both gas-side and liquid-side) must be increased to the
following table.
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increase the size of main pipes.
(Refer to figure below)
1. Outdoor unit
2. Main pipes
3. Increase
4. The first refrigerant branch kit
5. Indoor unit
4
1
5
2
3
Appendix
Total length (m)
Total length (m)
R=
of liquid piping
+
of liquid piping
×0.26
size at φ19.1
size at φ15.9
kg/m
Total length (m)
Total length (m)
+
+
of liquid piping
×0.059
of liquid piping
size at φ9.5
size at φ6.4
kg/m
Example for refrigerant branch using REFNET joint and REFNET header