kozy heat Lakefield 56150 Installation And Operation Manual page 11

Free-standing direct vent fireplace
Hide thumbs Also See for Lakefield 56150:
Table of Contents

Advertisement

HORIZONTAL TERMINATIONS
The minimum horizontal venting configuration is 3 ft. vertical
from the top of the fireplace followed by a 90-degree elbow,
then 1 ft. horizontal thru exterior wall.
VERTICAL
TERMINATIONS:
Minimum vertical vent run: 3 ft.
Maximum vertical vent run: 40 ft.
RESTRICTOR REQUIREMENTS:
Small restrictor: Straight vertical vent runs between 10' - 15'.
Large restrictor: Straight vertical vent runs between 15' - 40'.
PAGE 8