Powerware 9125 Two-in-One ® PowerPass Distribution Module ® User’s Guide For use with Powerware 9125 Two-in-One 5000/6000 VA UPS Models...
Page 2
Powerware and PowerPass are registered trademarks of Eaton Electrical Inc. Greenlee is a registered trademark of Greenlee Textron. ECopyright 2003–2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Page 3
92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact: Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland...
Page 4
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
For PDM models with hardwired outputs, suitably rated disconnect switches for the output AC circuit(s) are to be provided by others. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 8
For PDM systemer med hårdledningsudgange, skal overstrømsbeskyttelse for vekslestrømmens udgangskredsløb forsynes af andre. For PDM systemer med hårdledningsudgange, skal egnede, nominelle afbryderkontakter for vekslestrømmens udgangskredsløb forsynes af andre. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 9
Voor PDM systemen met vast-bedrade uitgangen, moet de overstroombeveiliging voor wisselstroom uitvoercircuit(s) door anderen worden geleverd. Voor PDM systemen met vast-bedrade uitgangen, moeten de juiste hoofdschakelaars voor wisselstroom uitvoercircuit(s) door anderen worden geleverd. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 10
Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi). PDM-järjestelmissä kiintealla asennuksella: kuormana olevien laitteiden ylivirtasuojaus ja erotuskytkimet tulee toteuttaa kuormapiireissa. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 11
Pour les models PDM ayant des sorties câblées, les interrupteurs de déconnexion convenables pour le(s) circuit(s) de sortie de courant alternatif doivent être fournie par un autre fournisseur. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 12
Für PDM-Systeme mit festverdrahteten Eingängen muß der Überstromschutz für die Ausgangswechselstromkreise anderweitig bereitgestellt werden. Für PDM-Systeme mit festverdrahteten Ausgängen müssen Trennschalter für die Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt werden. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 13
Nei sistemi PDM provvisti di uscite cablate, i sezionatori di corrente nominale adeguata per il/i circuito/i a corrente alternata in uscita devono essere forniti da terzi. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 14
For PDM systemer med fastkoplete uttak, må overstrømvern for vekselstrømuttak(ene) stilles til rådighet av andre. For PDM systemer med fastkoplete uttak, må passende utkoplingsbrytere for vekselstrømuttak(ene) stilles til rådighet av andre. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 15
Para sistemas PDM com saídas conectadas, interruptores de desconexão devidamente qualificados para circuitos de saída de corrente alternada devem ser fornecidos por outros. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 16
устройство защиты от перегрузки выходного контура (контуров) переменного тока приобретается отдельно. Для моделей ИБП с постоянно запаянными выходными контактами соответствующие размыкающие переключатели выходного контура (контуров) переменного тока приобретаются отдельно. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 17
CA de salida será suministrada por terceros. Para los sistemas PDM con salidas cableadas permanentemente, los interruptores de desconexión debidamente clasificados para el/los circuito(s) de CA de salida serán suministrados por terceros. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 18
Överströmsskydd för de utgående växelströmskretsarna ska tillhandahållas av andra för PDM-system med fasta utgångar. Bortkopplingsswitchar med passande dimensionering för de utgående växelströmskretsarna ska tillhandahållas av andra för PDM-system med fasta utgångar. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
UPS Setup The Powerware 9125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If the UPS is already installed and operating, shut down the UPS before installing the PDM.
Verify that the battery circuit breaker on the UPS rear panel is in the OFF position (see Figure 6 on page 18). Slide the battery trays into the chassis (see Figure 1). Figure 1. Installing the Battery Trays ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 21
If the UPS is in a rack and you are installing an optional EBM, continue to “EBM Installation” on page 18; otherwise, continue to “Hardwired PDM Installation” on page 19 or “Plug-Receptacle PDM Installation” on page 28. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Figure 4. Figure 4. Tower PDM Configuration Align each joining bracket with the adjacent cabinet screw holes and secure with the supplied screws (see Figure 5). ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 23
If you are installing an optional EBM, continue to the following section, “EBM Installation;” otherwise, continue to “Hardwired PDM Installation” on page 19 or “Plug-Receptacle PDM Installation” on page 28. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
NOTE Do not make unauthorized changes to the UPS or PDM; otherwise, damage may occur to your equipment and void your warranty. The Powerware 9125 hardwired models require a dedicated branch circuit that meets the following requirements: 40A minimum circuit with short circuit and overcurrent protection 200–240 Vac...
Page 27
NOTE In most applications, the voltage switch does NOT need changing. To change the switch position, remove the bracket screw and turn the switch. Flip the bracket around to fit the new position and reinstall. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 28
Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 9 mm (0.35I) of insulation from the end of each incoming wire. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 29
Source Input Line 2 UPS Output Line 1, 208–240V UPS Output Line 2, 208–240V Source Input Line 1 Output Input Ground Ground Figure 11. PPDM HW Model Terminal Block ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 30
11. Replace the wiring access cover and the conduit landing plate. 12. Plug the input and output cords of the PDM into the input and output power connectors on the UPS rear panel (see Figure 10). ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 31
NOTE If you installed power management software and optional EBMs, ensure maximum battery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E...
INSTALLATION Remote Emergency Power-off Installation The Powerware 9125 includes a REPO connector that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location. The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software.
Page 33
UPS output. For hardwired PDMs, return to Step 16 on page 25. For plug-receptacle PDMs, return to Step 10 on page 30. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
NOTE In most applications, the voltage switch does NOT need changing. To change the switch position, remove the bracket screw and turn the switch. Flip the bracket around to fit the new position and reinstall. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 35
L14-30R 5-15R PPDM L6-30&L14-30 Models Output Voltage Input Voltage 208V Switch Position Default 240V Switch Position (from UPS) (from UPS) L6-30R L14-30R 5-15R L6-30R L14-30R 5-15R ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 36
PDM rear panel. 11. Plug the UPS power cord into an L6-30 power outlet. μ indicator flashes, indicating the UPS is in Standby mode with the equipment offline. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 37
NOTE If you installed power management software and optional EBMs, ensure maximum battery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E...
NOTE The UPS exits Configuration mode automatically after two minutes of inactivity. Press and hold the On button and the button simultaneously for three seconds to exit Configuration mode at any time. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 42
Flashing Alarm DOES NOT sound when the polarity of the outlet (default) is reversed or the ground connection is missing. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Chapter 4 Operation NOTE Refer to the Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide for UPS operation. The PowerPass Distribution Module allows for the removal of the UPS while providing power to your protected equipment. This Maintenance Bypass feature is useful when replacing the UPS for maintenance or upgrades.
Page 44
The bar graph indicators display the percentage of load being applied to the UPS. The UPS is now in Normal mode and supplying power to your equipment. Reinstall the PDM front cover. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
(1) L6-30R, (1) L14-30R, 45A/240V PPDM L6-30&L14-30 PPDM L6-30&L14-30 208/240V 208/240V (4) 5 15R (4) 5-15R 208/240V Output voltage varies ±5% based on the attached load. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 46
EMC (Class A) EN 50091-2, FCC Part 15, ICES-003 Dimensions (WxDxH) 44.2 x 68.3 x 13 cm 17.4” x 26.9” x 5.1” (3U) Weight 46.7 kg (103 lb) ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. Help NOTE For critical applications, immediate replacement may be available. Call the Desk for the dealer or distributor nearest you. ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...
Page 56
SERVICE AND SUPPORT ® EATON Powerware 9125 Two-in-One PDM (5000/6000 VA) User’s Guide 164201519 Rev E www.powerware.com...