Fuse Ratings - GE LP 33 Series Operating Manual

60 – 80 – 100 – 120 kva 400 vac ce / series 2
Hide thumbs Also See for LP 33 Series:
Table of Contents

Advertisement

5.7.2 Fuse ratings

If ELCB breakers are prescribed to protect the input connections, consider the high leakage current
towards the earth generated by the noise-suppressor capacitors.
If strongly prescribed, the ELCB breakers should be the largest type suitable for non-linear current and
for delayed operation.
Common input Rectifier & Bypass
Fig. 5.7.2-1 Common input Rectifier & Bypass
UPS model
LP 33 Series 60 kVA
LP 33 Series 80 kVA
LP 33 Series 100 kVA
LP 33 Series 120 kVA
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
Fuses AgL or equivalent MTCB
for mains voltages 3x380/220V, 3x400/230V, 3x415/240V
F1
F2
3 x 100 A
3 x 100 A
3 x 125 A
3 x 125 A
3 x 160 A
3 x 160 A
3 x 200 A
3 x 200 A
Separate input Rectifier & Bypass
(optional)
Fig. 5.7.2-2 Separate input Rectifier & Bypass (optional)
F3
3 x 100 A
3 x 125 A
3 x 160 A
3 x 200 A
Operating Manual LP 33 Series 60-80-100-120 kVA / S2
F4 (external battery)
3 x 125 A
3 x 160 A
3 x 200 A
3 x 250 A
Page 34/103