Fuse Ratings - GE Digital Energy LP 33 Operating Manual

10 – 20 – 30 kva series 4
Hide thumbs Also See for Digital Energy LP 33:
Table of Contents

Advertisement

g
4.7.2

Fuse ratings

Fig. 4.7.2-1 Mains input and battery fuses
UPS model
LP 33 / 10 kVA
LP 33 / 20 kVA
LP 33 / 30 kVA
Required protective devices
If ELCB breakers are prescribed to protect the input connections, consider the high leakage current
towards the earth generated by the noise-suppressor capacitors.
If strongly prescribed, the ELCB breakers should be the largest type suitable for non-linear current
and for delayed operation.
Fig. 4.7.2-2 Common input mains
UPS model
LP 33 / 10 kVA
LP 33 / 20 kVA
LP 33 / 30 kVA
OPM_LPS_33E_10K_30K_4CN_V010.doc
Fuses type URD 660/690V
F1 - F2 - F3
20A (14 x 51)
40A (14 x 51)
63A (22 x 58)
Fuses (gL) or Circuit Breakers rating
for AC input 3x380/220V, 3x400/230V, 3x415/240V
F1
F2
3 x 25A
3 x 25A
3 x 50A
3 x 50A
3 x 63A
3 x 63A
LP 33 fuses
The UPS is equipped with rectifier input fuses
F1, F2, F3 and battery fuses F9, F10, F11.
In case of replacement the same type and the
same rating must be used (see table below).
Fuses type gG-gL 660/690V
Fig. 4.7.2- Separated input mains (option)
F3
3 x 20A
3 x 35A
3 x 50A
Operating Manual LP 33 / 10-20-30 kVA
28/82
F9 - F10 - F11
25A (14 x 51)
50A (14 x 51)
80A (22 x 58)
F4 (external battery)
2 x 25A
2 x 50A
2 x 80A