Discharge Temperature Release Control; Current Release Control - Carrier 30AWH004HB Service Manual

Table of Contents

Advertisement

Discharge temperature release control

1) This function controls the compressor frequency, when the discharge temperature has increased due to max load
condition or during PMV control. It subdivides the frequency control up to a unit of 0.6 Hz to stabilize the cycle.
2) When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts it after
2 minutes, 30 seconds (time guard). The error count is cleared when operation of 10 minutes without error occurs. If the
abnormal stop zone has been detected 4 times without clearing, an error code is displayed.
* Possible causes include excessive amount of refrigerant, defective PMV, or blockage in the refrigeration cycle.
30AWH004
30AWH006
30AWH008
30AWH012
30AWH015

Current release control

The output frequency and the output voltage are controlled by AC current detected on the P.C. board.
The max current value of the inverter are shown in table below.
[A]
Hold
Normal operation
SM_30AW.indd 64
TD[ C]
Error stop ("P03" displayed after 4 error counts)
a
b
c
d
e
As command
a
b
117
112
117
112
117
107
111
106
111
109
Frequency down
Hold
Control management
Frequency down
Frequency holding
Frequency slow-up
(Based on command)
c
d
e
108
105
98
108
105
98
103
100
93
100
95
90
106
103
96
l1 value [A]
COOL
30AWH004
6.3
30AWH006
8.5
30AWH008
10.1
30AWH012
23
30AWH015
20
64
TD: Discharge
temperature
HEAT
6.3
10.8
12
23
20
5
30AW