Defrost control (Only in heating opearation)

In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in A zone to D
zone.
a
b
27'70''
27'40''
29
29
34
40
39
45
A zone
Defrost operation is performed in this zone when TE0-TE ≥ 3**** continued for T seconds**
B zone
Defrost operation is performed in this zone when TE0-TE ≥ 3**** continued for T seconds**
C zone
Defrost operation is performed when this zone continued for T seconds**
D zone
Defrost operation is performed when this zone continued for T seconds**
* The minimum TE value between 10 and 15 minutes of compressor run time is stored inside the memory as TE0. TE0 is
calculated after each compressor restart in heating operation.
** 120 sec for sizes 004 , 006, 012
*** 2,5 for 004 and 006 sizes
****2,5 for 008 size
During the defrost:
The defrost operation is immediately finished if TE sensor temperature has become ε °C or more, or it also is also finished
when defrost operation has continued for τ minutes.
For 004, 006 and 008 sizes, defrost operation is also finished if TE is kept at+5°C or higher for 80seconds.
For 012 and 015 sizes, defrost operation is also finished if -7 ≤ TE < 12 has continued for 60 seconds.
After defrost operation has finished, the compressor and the outdoor fan start heating operation after stopped for approx.
50 seconds.
SM_30AW.indd 70
c
d
(A)
34'
-
-5
35
-
-4
55
90
-5
55
150
-5
size
004
006
008
Є [°C]
+8
τ [min]
15
Control management
(B)
(C)
(D)
-7
-
-20
-6
-10
-25
-10
-13
-18
-10
-2
-23
012
015
+12
10
70
5
TE: Entering
(in Heat
exchanger)
temperature
TE0: minimum
TE value
calculated 10-
15 min. after
each
compressor
restart in
heating
operation
Size 004-006
Size 008
Size 012
Size 015
30AW
14-03-2011 14:45:19