Custom Curves - Carrier 30AWH004HB Service Manual

Table of Contents

Advertisement

Custom curves

Parameters 112 and 117 set to 0 allows to load in the control a custom
climatic curve.
Below figures show which parameter of installer configuration table
need to be set to create customized heating and cooling curves.
NOTE: In case application requires fixed water set point in necessary to set an horizontal climatic curve by setting NUI code120=121 for Heating Climatic
Curve and 124=125 for Cooling Climatic Curve.
SM_30AW.indd 101
Carrier interfaces
1. CODE N° 121
2. CODE N° 120
3. CODE N° 118
4. CODE N° 119
5. CODE N° 125
6. CODE N° 124
7. CODE N° 123
8. CODE N° 122
101
7
30AW
14-03-2011 14:46:26