30AWH004HB/30AWH006HB/30AWH008HB/30AWH012HB/30AWH015HB 30AWH004XB/30AWH006XB/30AWH008XB/30AWH012XB/30AWH015XB 30AWH004NX/30AWH006NX/30AWH008NX/30AWH012NX/30AWH015NX SERVICE MANUAL Engineering Department of Italy November, 2010 SM_30AW.indd 1 14-03-2011 14:40:43...
General Informations Precautions for safety Ensure that all Local, National and International regulations are satisfied. maintain the unit to the customer. maintenance. regarding safety. Observe them without fail. Owner’s Manual. any problem. Follow the Owner’s Manual to explain how to use and Explanation of illustrated marks Indicates prohibited items.
General Informations 2.1 General precautions for safety maintain the heat pump. Inappropriate installation may result in water the weight adequately. leakage, electric shock or fire. the falling unit. so may cause electric shock. room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
Operation in heating Operation in cooling Outdoor air temperature [°C] Outdoor air temperature [°C] NOTE: For the 30AWH 004_ and 30AWH006_ units use a minimum External Air Temperature of +5 °C. (- -30AWH006_ ,-.-30AWH004_) 30AWH004HB 30AWH006HB 30AWH008HB 30AWH012HB 30AWH015HB MODEL NAME...
Installation Installation location INSTALLATION disruptive to your neighbours. SITING THE UNIT feet. WATWER CONNECTIONS be raised at least 200 mm above the usual snow level. CAUTION: ELECTRICAL CONNECTIONS wind like a coast or on a high storey of a building, ensure normal fan operation by using a duct or a wind shield.
Installation Minimum clearances Obstacle at rear side Upper side is free Single unit installation Obstacles at both right and left sides. or more or more Serial installation of two or more units or more or more or more or more Obstacle at rear side Obstacle also at the upper side or more...
Page 11
Installation Minimum clearances Obstacles at both front and rear sides Standard installation Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit. Serial installation of two or more units Single unit installation or more...
Installation 3.2 Preliminary operations 15 mm or less Knockout Drain nipple hole mounting hole Before installation, check strength and horizontality of the base so that If the unit is installed in a very windy place, protect the fan with a wind abnormal sound does not generate.
Installation 3.3 Water connections 3.3.1 Hydronic module The 30AWH__H units are equipped with an integrated hydronic module provided outside. In any case, all the necessary protections and valves that allows fast installation with the aid of a few external components. are to be inserted in the water circuit inside the unit.
Page 14
Installation 30AWH__X , 30AWH__NX integrated water circuit automatic purge valve flow switch safety valve (outlet 1/2’) temperature probe 30 AWH Unit Nominal water flow 0,20 0,28 0,33 0,58 0,69 Water loop content for 30AWH__X, According to 30AWH__NX expansion vessel installed Max water loop pressure Filling water...
Page 15
Installation 3.3.3 Typical hydraulic circuit diagrams Hydraulic circuit diagrams for 30AWH___H air flushing valve (in the highest parts of the circuit) line filter for water (10 mesh/cm^2) 3-way valve pressure gauges sanitary water accumulation tank filling valve inside system system drain valve (at the lowest points of the circuit) Hydraulic circuit diagrams for 30AWH___X and 30AWH___NX air flushing valve (in the highest parts of the circuit) line filter for water (10 mesh/cm^2)
Page 16
Installation 3.3.4 Available static pressure (H version) 30AWH006H 30AWH006H 30AWH004H WATER FLOW RATE (l/s) WATER FLOW RATE (l/s) 30AWH008H 30AWH012H - 30AWH015H 30AWH012H 30AWH008H WATER FLOW RATE (l/s) WATER FLOW RATE (l/s) 3.3.5 Water circuitpressure drop (X and NX version) 30AWH004X 30AWH006X 30AWH006X...
Page 17
Installation 3.3.6 Circulating water Pump (only H version) Water flow setting Pump Speed Setting procedure: The best speed setting will provide adequate circulation and provide Set the speed selector to minimum (one) Speed selector Open all thermostatic or manual radiator valves to maximum Set any room thermostatic controls to maximum Start up system and pump should start Shaft protection plug...
Page 18
Installation 3.3.8 Water loop charging, system cleaning and Water Characteristics Charge the water loop, with water, until the pressure on the hydro unit Looking for Code 111 (water flow switch status) the installer can verify if reads 0.15MPa (1.5bar ) the water fill operating is completed (when water is flowing, parameter Setting NUI Code104 (installation mode) = 1 water pump is forced on.
Page 19
Installation 30 AWH Unit 0,20 0,28 0,33 0,58 0,69 Nominal water flow Water loop content for 30AWH___H units Max water loop pressure Filling water pressure Max elevation 30AW upper Pipe water content Internal Diameter Outer diameter Liters / meter 12 mm 14 mm 0,11 l/m 14 mm...
Installation 3.4 Refrigerant schematics Refrigerant Circuit N° Component N° Component 4-way valve TR sensor TS sensor Liquid tank Check joint Pulse Motor Valve Accumulator Distributor Muffler TE sensor TD sensor TL sensor (only 015) DC twin rotary compressor Propellor fan BPHE TO sensor Muffler...
Page 21
Electrical connections All field electrical connections are the responsibility of the installer. WARNING Make water connections before electrical connections. Make ground connection prior to any other electrical connections 30AWH Unit 004_ 006_ 008_ 012_ 015_ Power supply V- ph - Hz 230 - 1 -50 Allowable Voltage Range 207 ÷...
Electrical connections 4.1 Auxiliary electrical connections Terminal Block H Version 33AW-CS1 Remote control Alarm Input C W G Y 23 24 1 2 3 6 7 8 21 22 C W G Y C W G Y 2 3 6 7 2 3 6 7 33AW-RC1 Remote control...
Page 23
Electrical connections Terminal Block NX Version 33AW-CS1 Remote control C W G Y C W G Y C W G Y 23 24 1 23 24 1 13 14 15 2 3 6 7 2 3 6 7 8 21 22 8 21 22 33AW-RC1 Remote control...
Electrical connections 4.1.2 External heat source An External Heat Source can be driven by Aquasnap Plus. When the OAT is less than second parameter both the HP and the For this feature is necessary install 33AW-CS1 interface EHS will be operative as per algorithm. Procedure to install an External Heat Source Connect electrically EHS to N and 4 terminals to a relay that drives mode and EHS is activated (eg.with par.148 = -2 EHS is activated with...
Page 25
4.1.6 External temperature probe If the positioning of the external unit could induce a non-representative 3kΩ @ 25°C, Carrier code: 33AW-RAS01) remote. Connect the terminals reading of the external temperature by the probe positioned on the of the probe between PINS 23 and 24 of the terminal strip.
Page 26
30AWH__H 33AW-CSI Description Signal Limits Installation Menu Code Additional external temperature probe 23 - 24 Input (NTC 3kΩ @25°C) N.A. Input (contact switch quality Sanitary Water Request 13 - 15 N.A. >25mA@12V) Input (contact switch quality Maximum Frequency Reduction Compressor 13 - 14 N.A.
4.2 Applications Heating Applications External Space heating heat source LWT 55° C Sanitary hot Mid temp radiator water LWT 45° C 60° C 33AW-CS1 INTERFACE Heat pump LWT 35° C outdoor unit Water temperature range produced by AQUASNAP Under floor heating air to water heat pump 20-60°...
GMC CONTROL Users can select the desired operating Control is based on the GMC platform developed by Carrier. For the the requests coming from Inverter control tuning chiller unit fan, PMV, 30AWH AquaSnap PLUS inverter chiller / heat pump a new GMC board compressor.
Page 57
Control management When power supply is reset When a unit is powered up, depending on its Auto Start configuration, it will start up with its last operating parameters, or OFF Mode. The EEPROM is available for saving the operating environment of the control in the event of a power-reset condition. If not configured for auto start, at the power up the system will remain in OFF Mode.
Control management Operating mode selection The operating mode is selected based on the command chosen by the remote control. OAT: Outdoor Temperature Cooling Mode WSP: Water Set Point Depending by the system configuration and when the operating mode is cool, the system could operate as follows: With Comfort NUI (CS1).
Control management Dehumidifier activation (X and H terminal block pins 11 – N) External dehumidifier source is based on NUI Relative Humidity value, (For this feature is necessary install 33AW-CS1 NUI code 108 and 107 interface). Two codes shall be accesses through NUI: Code 108: It is for defining availability of external dehumidifier.
Page 60
Control management High Temperature Protection When the water starts to get to hot, this is a sign that the pressure in the system is increasing. Certain actions are taken to decrease the pressure. Max(Actual Water Temperature Entering, Actual Water Compressor OFF Temperature 62 °C Exiting)
Page 61
Control management Unit Status and Defrost output or Tair Setpoint status Based on the NUI code 147 set-up, the Output J7 Pin 2 (N-5 on the terminal block) could play for one of these Functions: NUI code 147 - ALARM: The intent of this output is to point out the alarm condition. This signal could be used by an external control to verify if the Unit is able to operate with the requested function.
Page 62
Control management Backup External Heat Source functionality (X and H terminal block pins 5 – N) This functionality is valid when user mode is HEATING MODE. SHW: Sanitary Hot Between pins 5 and N of terminal strip (see paragraph 4.1) an output is available (1 ph ~ 230V, 2A max) to activate a Water backup external heat source (such as Electric Heater or Boiler).
Page 63
Control management System Diagnostics The control contains diagnostic tests to verify the integrity of the system. Recoverable: The On Board LED is located on the circuit board. It is used to display normal operation status and diagnostic fault code self healing information.
Control management Discharge temperature release control 1) This function controls the compressor frequency, when the discharge temperature has increased due to max load TD: Discharge temperature condition or during PMV control. It subdivides the frequency control up to a unit of 0.6 Hz to stabilize the cycle. 2) When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts it after 2 minutes, 30 seconds (time guard).
Control management Outdoor fan control Allocations of fan tap revolutions FAN TAP 30AWH004 30AWH006 30AWH008 30AWH012 Higher fan 30AWH012 Lower fan 30AWH015 Higher fan 30AWH015 Lower fan 1) Cooling fan control 004-006 sizes. The blowing air volume is controlled as follow: When strong wind blows at outdoor side, the operation of heat pump continues with the fan motor stopped.
Page 66
Control management The output frequency and the output voltage are controlled by AC current detected on the P.C. board. The max current value of the inverter are shown in table below. TE( C) +30 rpm/20 sec. Hold zone -30 rpm/20 sec. TO <...
Page 67
Control management 2) Heating fan control 004-006 sizes The blowing air volume at the outdoor unit side is controlled as follow: 1. When strong wind blows at outdoor side, the operation of heat pump continues with the fan motor stopped. 2.
Page 68
Control management Coil heating control (compressor warm up process) TO: Outdoor crankcase heater. The control purpose is to prevent slackness of refrigerant inside the compressor. Temperature TE: Entering the system when the control has interrupted the compressor warm up process. (in Heat 3.
Page 69
Control management High-Pressure suppression TE control 1. This control routine suppresses that pressure which becomes abnormally too high during the cooling operation. TE: Entering (in Heat guard) if TE < 67°C, the compressor is enable to restart. After the compressor restart, the unit current is continuously con- exchanger) temperature The error counter will be cleared if TE <...
Page 70
Control management Defrost control (Only in heating opearation) In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in A zone to D TE: Entering zone. (in Heat exchanger) temperature TE0: minimum TE value calculated 10- 15 min.
Diagnostic 6.1 Diagnostic 6.1 Inverter alarms 6.1.1 Error codes 30AWH012 only Troubles of the unit can be diagnosed by LED indications on the cycle interrupted on the serial circuit. If the case thermostat operation happens control P.C. board of the unit. When multiple errors are detected, the continuously, a serial communication error occurs because of a serial latest error is displayed.
Page 72
Diagnostic 6.1.2 Error codes 30AWH015 only c) If there is an error, any of LED D800 to D804 goes on. (Display 1) The error which is generating at present and the latest error (Latest error d) When pushing the pushdown button switch SW800 for approx. 1 information including present) second, the display is exchanged.
Page 73
Diagnostic The values detected by the controller, such as temperature sensor or current value are simply confirmed. (Legend) D800 (Yellow) D803 (Yellow) : Go off, : Go on D801 (Yellow) D804 (Yellow) D802 (Yellow) D805 (Green) Temperature sensor (°C) Compressor Current operation opening...
Diagnostic 6.2 GMC alarm codes There is a LED on the GMC board that displays any board errors. The the flashing is interrupted for 2 seconds between the first and second error code can be identified from the flashing LED using the following digits.
Page 75
Diagnostic NOTE: Unit status OFF means that unit immediately stops. 6.3 GMC I/O PERIPHERAL INPUT DEVICE DESCRIPTION Reference Type Units Water Enter Exchanger Sensor (Analog) Volts Sensor Refrigerant Sensor Sensor (Analog) Volts Water Exit Exchanger Sensor (Analog) Volts Sensor Outdoor Air Sensor J22 Pin 1-2 Sensor (Analog) Volts...
Page 76
Water Temp (J6A) Alarm + Defrost / Dehumidifier output (J7 Pin 4) Water Pump Speed 1 (J7, Pin1) Carrier Alarms Defrost / TFC output (J7, Pin2) Ext. Heat Source / Defrost Output (J7, Pin 3) Monobloc High Voltage 3 Way Valve ( J4, Pin5 )
Diagnostic 6.4 Troubleshooting Fault code 3 – Enter Water Temperature sensor fault Is the TA sensor correctly connected? Correctly connect the TA Sensor (See Wiring Diagrams) Are the resistance characteristics of the Replace defective TA Sensor temperature sensor TA normal?* * Check resistance curve Check indoor P.C.
Page 78
Diagnostic Fault code 6 – Loss communication to NUI control Are the connections of NUI and GMC board Check and correct the connections correct Are all cables and connectors correctly Check cabling between NUI and GMC fitted board Check GMC Board - if defective, replace Check NUI error - if defective, replace Fault code 7 –...
Page 79
Diagnostic Fault code 9 – Flow Switch error / Water Pump Flow switch is Connect flow switch Pump rotates connected to board connector to board Perform air vent Excess air noise comes from inside the pump Built-in pump is Connect pump connected to board connector to board Flow switch is...
Page 80
Diagnostic Fault code 13 – Loss communication to RS485 Are the connections correct Check and correct the connections (See Wiring Diagrams) Check cabling Are all cables and connectors correctly fitted Check GMC Board - if defective, replace Fault code 14 – Loss of signal from inverter board Are the connections of inverter board and Check and correct the connections GMC board correct (See Wiring Diagrams)
Page 81
Diagnostic Fault code 17 – Inverter Air sensor fault Is the sensor correctly connected Correctly connect the Sensor (See Wiring Diagrams) Are the resistance characteristics of the Replace defective Sensor temperature sensor normal * Check Inverter board - replace if defective *Check resistance table Fault code 18 –...
Page 82
Diagnostic Fault code 21 – Inverter current sensor fault Is the power supply cabling and sensor Check and correct cable cabling correct? (See Wiring Diagrams) Check inverter board Fault code 22 – Heat exchanger Sensors TE/TS Are the sensors correctly connected? Correctly connect the Sensors (See Wiring Diagrams) Are the resistance characteristics of the...
Page 83
Diagnostic Fault code Fault code 24 – Outdoor fan motor error– Compressor lock Are connectors CN300, CN301, CN302 and CN303 connected correctly?* Is it possible to freely rotate the fan with hands when CN300, CN301, CN302 & CN303 are disconnected?* Normal resistance value between leads: Between (1) (Red lead) and (2) (White lead) Between (2) (White lead) and (3) (Black lead)
Page 84
Diagnostic Fault code 27 – Compressor lock a t l power supply voltage Are the connections of cables and Check and correct the connectors correct cabling & connections Is the compressor Has there been a refrigerant Compressor lock - replace functional leak Check TE and TS Sensors, replace...
Page 85
Diagnostic Fault code 29 – Compressor break down Correct the power supply Is the power supply voltage normal voltage Delete the cause of Does and overload condition exist overload Check and correct circuit Is the current detected by the current sensor cables normal Check P.C.
Page 86
Diagnostic Fault code 14 – High temperature release Does the unit operate Correct inter-connecting Are the inter-connecting cabling cables correctly wired Are the connectors Check P.C. Board - if Ensure connectors are correctly located defect, replace located correctly Is a DC Voltage of 280V Does the voltage measured measured between the between _and _ on the...
Page 87
Diagnostic 6.4.1 Relational graph of temperature sensor resistance value and temperature For 004, 006, 008, 012, sizes TR, TA sensor Resistenc e [k ] Ω Temperature [° C] TE,TO,TS sensor Ω Ω Resistence [k ] Resistence [k ] T<10° C T >10°...
Page 88
Diagnostic For 004, 006, 008, 012, 015 sizes LWT,EWT sensors Resistence [k ] Resistence [k ] Ω Ω T>50° C T<50° C Temperature [° C] Only 015 size TR, TA, TE, TS,TO sensors Resistence [k ] Ω Temperature [° C] TD, TL sensor Resistence [k ] Ω...
Page 89
Diagnostic 6.4.1 Resistance values of main components T ref T ref T ref T ref T ref Ω Ω Ω Ω Ω [°C] [°C] [°C] [°C] [°C] 46±4 46±4 46±4 46±3 46±3 4 Way 1795±150 1795±150 1765±150 1774±150 1489±150 22±2 22±2 22.4±2 35.2±2...
Carrier interfaces The AquaSnap PLUS can use the following user interfaces: the 33AW-CS1 Comfort Series programmable thermostat the Carrier Dealer Service Tool. 7.1 Dry contacts control 30AW SM_30AW.indd 90 14-03-2011 14:45:45...
Carrier interfaces 7.2 33AW-RC1 user interface WARNING: will supply power to the remote controller. Electrical shock can cause personal injury or death. - Open the remote controller rear mounting base to expose mounting holes. The base can be removed to simplify mounting (snap apart carefully at hinge to separate mounting base from remainder of the remote controller).
- Floating WSP based on OAT Climatic Curve can be selected (Installer External Heat Source customized CC or predefined Carrier CC) code 112, 117-125 When an EHS is requested a 230V output is energized to drive an external heat source...
Page 93
Carrier interfaces Carrier’s NUI series programmable user interface is wall-mounted, Install User Interface low-voltage user interface which maintains room temperature by controlling the operation of a heating and/or air conditioning system. Turn OFF all power to unit. If an existing User Interface is being replaced: present versions.
Page 94
Carrier interfaces 7.3.1 Main functions User functionality (comfort): tool for 10 sec) 7.3.2 Displayed icons Child lock Compressor ON / Frequency reduction Sanitary Hot Room air Water Mode temperature Back-up EHS mode Home anti-freeze mode On / Off Timer on...
Carrier interfaces 7.3.3 Control buttons Mode Up & down Hold Zone Done Home Sleep Away Day/hour/min Days Period Start time For more details refer to specific manuals. 7.3.4 Codes table VALUE RANGE Code Nr. Name DESCRIPTION STANDARD This code is use to select the Unit Mode: MODE 2.
Page 96
Carrier interfaces VALUE RANGE Code Nr. Name DESCRIPTION STANDARD This code displays the Outdoor Air Temperature. The valid OAT OUTDOOR value is used with this priority: -30°C 90°C TEMPERATURE 1. OAT from GMC thermistor (if it is installed) 2. OAT from inverter, read by TO sensor.
Page 97
Carrier interfaces VALUE RANGE Code Nr. Name DESCRIPTION STANDARD This code is use to select the output connected at PIN 11 on ALARM-DEFROST OR terminal strip: HUMIDITY 1. Unit alarms and/or Defrost SELECTION 2. Humidity Control FROST DELTA This code is use to set the frost delta set-point used by the Anti 0°C...
Page 98
Carrier interfaces VALUE RANGE Code Nr. Name DESCRIPTION STANDARD REAL FREQUENCY This code displays the real compressor frequency COMPRESSOR This code displays the working on hours of the compressor.. RUNTIME CDU CAPACITY This code displays the nominal heat pump capacity [kW].
Page 99
Carrier interfaces VALUE RANGE Code Nr. Name DESCRIPTION STANDARD This code is use to define the external heat source status when EHS is activated and OAT < temperature value set in Code 148: 0. Always On EXTERNAL HEAT SOURCE STATUS perature set-point(same hysteresis of Thermostat function).
Page 101
Carrier interfaces Custom curves Parameters 112 and 117 set to 0 allows to load in the control a custom climatic curve. Below figures show which parameter of installer configuration table need to be set to create customized heating and cooling curves.
Maintenance 8.1 Refrigerant charge check IMPORTANT: All maintenance operations must be performed by qualified personnel. This check becomes necessary after any refrigerant leak or after IMPORTANT: replacement of the compressor. - Never charge refrigerant exceeding the specified amount. The best method to correctly charge refrigerant is to completely empty - If the specified amount of refrigerant cannot be charged, charge the refrigerant circuit using refrigerant recovery equipment.
Maintenance 8.3 Replacement of the main parts N° Exchange Work procedure (IMPORTANT: Ensure gloves are parts worn at all times to avoid risk of injury) Remarks name 30 AWH 004, 30 AWH 006, 30 AWH 008 Common Detachment procedure switch of the breaker. After unscrewing the screws, remove the front panel while drawing it downward.
Page 104
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Inverter Inverter cover assembly 1. Perform the works from 1 to 4 of (1) and (2) . WARNING disassemble the inverter to prevent an electric shock. Perform discharging by connecting the discharging resistance or plug of soldering iron to + , –...
Page 105
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Reactors 1. Perform the works from 1 to 4 of (1) and (2). Connector 2. Remove the inverter assembly item (4). 3.
Page 106
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Compressor Perform the works from 1 to 4 of (1) and (2), (3), (4), (6), (7). Piping panel 1. Discharge refrigerant gas. Screws also the nut fixing the liquid receiver and the parti- tion plate.
Page 107
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name (11) Pulse modula- 1. Perform the works from 1 to 4 of (1) and (3). ting 2. Hold outside of the coil by hands and turn it while valve lifting upward.
Page 108
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Water CAUTION: To replace a water circuit part, first close the water circuit supply source valve and the valve of water pipe connected to the unit.
Page 109
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name (15) Automatic 1. Perform works from 1 to 4 of (1) and (2). purge 2. Remove the automatic purge valve. valve IMPORTANT After the automatic purge valve replacement repair,...
Page 110
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name (19) Pump 1. Perform works from 1 to 4 of (1) and (2). (Only H 2. Remove the relative connectors Pump motor versions) 3.
Page 111
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Air-outlet cabinet Heat exchanger 1. Perform the work from 1 to 4 of (1). 2. Remove the screws for the air-outlet cabinet and 3.
Page 112
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Cycle PC 1. Perform the works from 1 to 4 of (1) ,(3) and (4). board 2. Remove connectors and lead wires: (012) Connector CN800: Connection with IPDU P.C.
Page 113
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Reactors 1. Perform the works from 1 to 4 of (1) and (2). Partition plate (012) 2. Remove the inverter assembly item (4). 3.
Page 114
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name Reactor 1. Perform the works from 1 to 4 of (1) and (2). Bundling band (Compressor lead, Reactor lead) 2.
Page 115
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name (11) Fan motor 1 Perform the works from 1 to 4 of (1) and (3). Flange nut propeller. Lose the flange nut by turning clockwise. (To tighten the flange nut, turn counter-clockwise.) 3.
Page 116
Maintenance N° Exchange Work procedure (IMPORTANT: Ensure gloves are Remarks parts worn at all times to avoid risk of injury) name (13) Liquid 1. Perform the works from 1 to 4 of (1) and (2), receiver (3), (4), (5), (8). 2.
Page 117
Maintenance N° Remarks Work procedure (IMPORTANT: Ensure gloves are Remarks worn at all times to avoid risk of injury) Expansion vessel (15) Water CAUTION: circuit To replace a water circuit part, first close the water supply source valve and the valve of water pipe connected to the unit.
Page 118
N° Remarks Work procedure (IMPORTANT: Ensure gloves are Remarks worn at all times to avoid risk of injury) (19) Flow 1. Perform works from 1 to 4 of (1) and (2). switch 2. Remove the relative connector 3. Remove the flow switch. CAUTION: The flow switch connection uses an O ring for water water leakage may occur.
8.4 Periodic Inspection Items Unit Frequency Periodic inspection details Insulation measurement (Power source circuit/ Annually Insulation measurement with a mega tester Compressor) Operation check Annually Hot water supply/ Heating/ Cooling operation check with remote controller. Refrigerant leakage/ Water leakage inspection. Annually Visual inspection and check with a leak tester: No leakage must be found.
Page 138
L010129H30-0111 Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1 The manufacturer reserves the right to change any product specifications without notice. November, 2010 Supersedes October, 2008. Printed in Italy SM_30AW.indd 138 14-03-2011 14:47:25...