Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 Operation And Service Manual

Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 Operation And Service Manual

Air-cooled chillers with comfortlink controls
Hide thumbs Also See for AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060:
Table of Contents

Advertisement

Controls, Start-Up, Operation,
Service, and Troubleshooting
CONTENTS
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . .2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Conventions Used In This Manual. . . . . . . . . . . . . . . . . . . .3
Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-44
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Main Base Board (Mbb) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Energy Management Module (Emm) . . . . . . . . . . . . . . . .19
Current Sensor Board (Csb) . . . . . . . . . . . . . . . . . . . . . . .19
Aux Board (Aux) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Expansion Valve Board (Exv) . . . . . . . . . . . . . . . . . . . . . .19
Enable/Off/Remote Contact Switch . . . . . . . . . . . . . . . . .19
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . .19
Board Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Control Module Communication . . . . . . . . . . . . . . . . . . . .19
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
• COOLER LEAVING FLUID SENSOR
• COOLER ENTERING FLUID SENSOR
• COMPRESSOR RETURN GAS
TEMPERATURE SENSOR
• OUTDOOR-AIR TEMPERATURE SENSOR (OAT)
• DISCHARGE TEMPERATURE THERMISTOR (DTT)
• REMOTE SPACE TEMPERATURE SENSOR OR DUAL
LEAVING WATER TEMPERATURE SENSOR
Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .29
Loss-Of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .29
Electronic Expansion Valves (Exv) . . . . . . . . . . . . . . . . .29
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LEAD/LAG DETERMINATION
• CAPACITY CONTROL OVERRIDES
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Operation of Machine Based on Control Method
and Cooling Set Point Selection Settings. . . . . . . . .32
Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .34
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Cooler Pump Sequence Of Operation . . . . . . . . . . . . . . .35
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT
(4 to 20 mA Controlled)
• DEMAND LIMIT (CCN Loadshed Controlled)
Cooling Set Point (4 To 20 Ma). . . . . . . . . . . . . . . . . . . . . .43
Digital Scroll Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
• DIGITAL SCROLL OPERATION
• DIGITAL COMPRESSOR CONFIGURATION
Pre-Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01
(Ccn) Interface . . . . . . . . . .19
®
Printed in U.S.A.
AQUASNAP
with COMFORTLINK™ Controls
System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Page
Start-Up And Operation . . . . . . . . . . . . . . . . . . . . 45,46
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Check Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . 45
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• TEMPERATURES
• LOW AMBIENT OPERATION
• VOLTAGE — ALL UNITS
Operation Sequence . . . . . . . . . . . . . . . . . . . . . .46,47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-63
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• CONTROL COMPONENTS
Electronic Expansion Valve (Exv) . . . . . . . . . . . . . . . 47
Exv Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 47
• FIELD SERVICING INSTRUCTIONS
• VALVE REPLACEMENT
• VALVE REASSEMBLY
Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
• BRAZED-PLATE COOLER HEAT EXCHANGER
REPLACEMENT
• BRAZED-PLATE COOLER HEAT EXCHANGER
CLEANING
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Microchannel Heat Exchanger (MCHX)
Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Check Refrigerant Feed Components . . . . . . . . . . . . . . 50
• FILTER DRIER
• MOISTURE-LIQUID INDICATOR
• MINIMUM LOAD VALVE
• PRESSURE RELIEF DEVICES
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
• HIGH-PRESSURE SWITCH
• PRESSURE TRANSDUCERS
• COOLER FREEZE-UP PROTECTION
• HEATER CABLE
• WINTER SHUTDOWN
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 53
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
• GENERAL OPERATION
• CONFIGURATION
• DRIVE PROGRAMMING
• EPM CHIP
• LOSS OF CCN COMMUNICATIONS
• REPLACING DEFECTIVE MODULES
Hydronic Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63,64
Recommended Maintenance Schedule . . . . . . . . . . . . . 63
Microchannel Heat Exchanger (MCHX)
Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64-73
Form 30RAP-2T
30RAP010-060
®
Air-Cooled Chillers
V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 58
®
Pg 1
12-10
Page
Replaces: 30RAP-1T

Advertisement

Table of Contents

Troubleshooting

loading

Summary of Contents for Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060

  • Page 1 ® Carrier Comfort Network Sensors ..........20 •...
  • Page 2: Safety Considerations

    CONTENTS (cont) Complete Unit Stoppage and Restart ....64 • GENERAL POWER FAILURE • UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS • CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN • OPEN 24-V CONTROL CIRCUIT BREAKERS •...
  • Page 3: General

    The CCN (Carrier Comfort Network referenced in the local display tables for users configuring the unit with CCN software instead of the local display. The CCN tables are located in Appendix B of the manual.
  • Page 4 ACCESSORY NAVIGATOR™ DISPLAY MODULE — The Navigator module provides a mobile user interface to the ComfortLink™ control system, which is only available as a field-installed accessory. The display has up and down arrow keys, an key, and an ENTER ESCAPE used to navigate through the different levels of the display structure.
  • Page 5 Table 2 — Scrolling Marquee Display Menu Structure* SERVICE MODE TEMPERATURES PRESSURES STATUS TEST Auto Service Ent and Leave Unit View of Test Mode Temps Run Status (TEST) (UNIT) (VIEW) Unit Run Outputs Temperatures Hour and and Pumps Start (OUTS) (CIR.A) (RUN) Compressor...
  • Page 6 Table 3 — Run Status Mode and Sub-Mode Directory KEYPAD SUB-MODE ITEM DISPLAY SUB-ITEM ENTRY XXX.X F VIEW ENTER XXX.X F XXX.X F SETP XXX.X F CTPT LOD.F STAT LD.PM YES/NO LS.AC YES/NO MODE YES/NO XXX % STGE ALRM TIME XX.XX MNTH DATE...
  • Page 7 Table 3 — Run Status Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY SUB-ITEM ENTRY PM (cont) ENTER STRN ENTER ENTER ENTER COIL ENTER ENTER ENTER VERS ENTER AUX1 MARQ NAVI *Press simultaneously to obtain version number. ENTER ESCAPE DISPLAY SUB-ITEM DISPLAY PMDT...
  • Page 8 Table 4 — Service Test Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY TEST ENTER OUTS ENTER CMPA ENTER CMPB ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. ITEM DISPLAY ON/OFF...
  • Page 9 Table 5 — Temperature Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY UNIT ENTER CIR.A ENTER CIR.B ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 6 —...
  • Page 10 Table 8 — Inputs Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY GEN.I ENTER CRCT ENTER 4-20 ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 9 —...
  • Page 11 Table 9 — Outputs Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ENTRY A.EXV ENTER B.EXV ENTER CIR.A ENTER CIR.B ENTER NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Table 10 —...
  • Page 12 Table 10 — Configuration Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY UNIT ENTER OPT1 ENTER ITEM DISPLAY SIZE SZA.1 SZA.2 SZA.3 SZA.4 SZB.1 SZB.2 SZB.3 SZB.4 XX.X F SH.SP FAN.S YES/NO EXV MODULE INSTALLED? YES/NO A1.TY COMPRESSOR A1 DIGITAL? MAX.T 0 to 12 MAXIMUM A1 UNLOAD TIME UNIT OPTIONS 1 HARDWARE...
  • Page 13 Table 10 — Configuration Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM ENTRY OPT2 CTRL ENTER LOAD LLCS LCWT DELY ICE.M LS.MD LS.ST LS.ND LS.LT CCNA ENTER CCNB BAUD HP.A ENTER A1.DT A2.DT HP.B B1.DT ENTER B2.DT ITEM DISPLAY EXPANSION UNIT OPTIONS 2 CONTROLS CONTROL METHOD LOADING SEQUENCE SELECT...
  • Page 14 Table 10 — Configuration Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ENTRY EXV.A ENTER EXV.B ENTER ENTER * Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500. ITEM DISPLAY CIR A EXV CONFIGURATION STR.A EXV CIRC.A START POS MIN.A EXV CIRC.A MIN POSITION XXXXX...
  • Page 15 Table 10 — Configuration Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY ENTRY RSET CRST ENTER XX.X F MA.DG XXX.X F RM.NO XXX.X F RM.F XX.X F RM.DG XXX.X F RT.NO XXX.X F RT.F XX.X F RT.DG DMDC DM20 SHNM SHDL SHTM...
  • Page 16 Table 10 — Configuration Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM ENTRY BCST T.D.BC ENTER OAT.B G.S.BC BC.AK Table 11 — Time Clock Mode and Sub-Mode Directory KEYPAD SUB-MODE ITEM DISPLAY ENTRY TIME HH.MM XX.XX ENTER DATE MNTH ENTER YEAR XXXX STR.M...
  • Page 17 Table 11 — Time Clock Mode and Sub-Mode Directory (cont) KEYPAD SUB-MODE ITEM DISPLAY ENTRY OVR.T ENTER OVR.L T.OVR YES/NO Table 12 — Operating Mode and Sub-Mode Directory KEYPAD SUB-MODE ENTRY MODE ENTER LEGEND — Chillervisor System Manager — Saturated Condensing Temperature —...
  • Page 18 Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed schedule, forcing unit to Occupied mode. Override can be implemented with unit under Local (Enable) or CCN (Carrier Comfort Network Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat- urated Suction Temperature is not increasing greater than 1.1°...
  • Page 19: Main Base Board (Mbb)

    MBB are shown in Table 17. Information is transmitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). The CCN (Carrier Com- fort Network) bus is also supported. Connections to both LEN and CCN buses are made at the LVT (low voltage terminal).
  • Page 20: Sensors

    The space temperature sensor includes a terminal block (SEN) and a RJ11 female connector. The RJ11 connector is used access into the Carrier Comfort Network To connect the space temperature sensor (Fig. 10): 1.
  • Page 21 Units on the CCN can be monitored from the space at the sensor through the RJ11 connector, if desired. To wire the RJ11 connector into the CCN (Fig. 11): IMPORTANT: The cable selected for the RJ11 connector wiring MUST be identical to the CCN communication bus wire used for the entire network.
  • Page 22 LOCATED OVER EMM AND EXV COMPRESSOR CONTROL BOX a30-4962 Fig. 3 — Typical Control Box for 30RAP010,015 Fig. 4 — Typical Control Box for 30RAP018-030 a30-4963 CSB-A1 C-A1 FB-1 CCB-1 FB-3 CSB-A1 CWP1 C-A1 CWP1 CWP2 FC1/MM FB-1 TRAN DISCONNECT OPTION/TB CWP1 CWP2...
  • Page 23 a30-4964...
  • Page 24 STANDARD OPTIONAL TERMINAL DISCONNECT BLOCK CB1A TB1A EQUIP GND TRAN3 SECONDARY 115V GRN/YEL GFI-CO FIOP/ACCESSORY LINE BRASS SCREW BRASS SCREW SILVER SCREW SILVER SCREW RESET TERMINAL TERMINAL VOLTAGE SERIES CONNECTIONS CONNECTIONS FOR TEST FOR PRIMARY SIDE SECONDARY SIDE 575-3-60 H1-H2 230-3-60 400,500 H2-H4...
  • Page 25 5.2 AMPS J10A RLY 11 RLY 9 RLY 10 J10B RLY 5 RLY 6 RLY 7 RLY 8 HPS-A RLY 1 RLY 2 RLY 3 RLY 4 HEAT ALMR HEAT/BOILER FIELD INSTALLED WIRING CWFS CWPI NOTE 8 MAIN BASE BOARD ENABLE REMOTE ON-OFF...
  • Page 26 STANDARD OPTIONAL TERMINAL DISCONNECT BLOCK CB1A TB1A EQUIP GND TRAN3 SECONDARY 115V GRN/YEL GFI-CO FIOP/ACCESSORY LINE BRASS SCREW BRASS SCREW SILVER SCREW SILVER SCREW RESET TERMINAL TERMINAL VOLTAGE SERIES CONNECTIONS CONNECTIONS FOR TEST FOR PRIMARY SIDE SECONDARY SIDE 575-3-60 H1-H2 230-3-60 400,500 H2-H4...
  • Page 27 a30-5284 5.2 AMPS J10A RLY 11 RLY 9 RLY 10 HPS-B J10B RLY 5 RLY 6 RLY 7 RLY 8 HPS-A RLY 1 RLY 2 RLY 3 RLY 4 HEAT ALMR HEAT/BOILER FIELD INSTALLED WIRING CWFS CWPI NOTE 9 MAIN BASE BOARD ENABLE...
  • Page 28 SPT (T10) PART NO. 33ZCT55SPT SENSOR Fig. 10 — Typical Space Temperature Sensor Wiring GREEN LED - YELLOW LED - LEN (LOCAL EQUIPMENT NETWORK) CCN (CARRIER COMFORT NETWORK) STATUS Fig. 8 — Main Base Board a30-4968 TO CCN COMM 1 BUS (PLUG) AT UNIT Fig.
  • Page 29: Energy Management Module

    Energy Management Module (Fig. 12) — factory-installed option (FIOP) or field-installed accessory is used for the following types of temperature reset, demand limit, and/or ice features: • 4 to 20 mA leaving fluid temperature reset (requires field-supplied 4 to 20 mA generator) •...
  • Page 30 CEBD430351-0396-01C STATUS RED LED - STATUS LEAD/LAG DETERMINATION — This is a configurable choice and is factory set to be automatic for all units unless the unit is equipped with a digital scroll compressor or minimum load, then circuit A is lead (Configuration The value can be changed to Circuit A or Circuit B leading as desired.
  • Page 31 Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve CONTROL 30RAP UNIT SIZE *Minimum Load Valve energized. STANDARD DEADBAND LEGEND LWT — Leaving Water Temperature CAPACITY STEPS STEPS % Displacement NOTE: These capacity steps may vary due to different capacity staging sequences.
  • Page 32: Head Pressure Control

    Cooler Freeze Protection — The control will try to prevent shutting the chiller down on a Cooler Freeze Protection alarm by removing stages of capacity. If the cooler fluid selected is Water, the freeze point is 34 F (1.1 C). If the cooler fluid selected is Brine, the freeze point is the Brine Freeze Point (Set ...
  • Page 33: Cooling Set Point Select

    30RAP UNIT SIZE 010,015 018-030 035-050 055,060 Two other control methods are available for Machine On/ Off control: OCCUPANCY SCHEDULE (Configuration  CTRL = 2) — The main base board will use the operating schedules as defined under the Time Clock mode in the scroll- ing marquee display.
  • Page 34: Low Sound Mode Operation

    Table 21 — Control Methods and Cooling Set Points CONTROL OCCUPANCY TYPE STATE (CTRL) Occupied 0 (switch) Unoccupied Occupied 2 (Occupancy) Unoccupied Occupied 3 (CCN) Unoccupied *Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed. †Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.
  • Page 35: Cooler Pump Sequence Of Operation

    Cooler Pump Sequence of Operation — time the unit is in an ON status, as defined by the one of the following conditions, the cooler pump relay will be enabled. 1. The Enable-Off-Remote Switch (CTRL=0). 2. Enable-Off-Remote Switch in REMOTE with a Start-Stop remote contact closure (CTRL=0).
  • Page 36 20, for wiring. The CCN communication bus must be connected between the two chillers. Connections can be made to the CCN screw terminals on LVT. Refer to Carrier Comfort Network Interface section, page 19, for wiring infor- ®...
  • Page 37 Table 22 — Dual Chiller Configuration (Master Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISP UNIT OPT1 ENTER OPT2 CTRL ENTER ESCAPE CCNA ENTER CCNB ENTER ESCAPE ENTER LLEN ENTER ENTER LLEN ENTER ESCAPE MSSL ENTER ESCAPE RSET SLVA ENTER ENTER SLVA ENTER ESCAPE...
  • Page 38: Temperature Reset

    Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont) SUB-MODE ITEM KEYPAD ENTRY LLBL ENTER ESCAPE LLBD ENTER ESCAPE RSET LLDY ENTER ENTER LLDY ENTER ESCAPE ESCAPE PARA ENTER NOTES: 1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN. 2.
  • Page 39 Table 23 — Dual Chiller Configuration (Slave Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISP UNIT OPT1 ENTER OPT2 CTRL ESCAPE CCNA ENTER ENTER CCNA ENTER ESCAPE CCNB ENTER ESCAPE ENTER LLEN ENTER ENTER LLEN ENTER ESCAPE RSET MSSL ENTER ENTER MSSL ENTER ESCAPE...
  • Page 40 KEYPAD SUB-MODE ITEM ENTRY CRST ENTER RSET MA.DG NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required. Table 25 —...
  • Page 41 Table 26A — Configuring Outdoor Air and Space Temperature Reset MODE KEYPAD SUB- (RED LED) ENTRY MODE DISP ENTER UNIT OPT1 OPT2 HP.A HP.B EXV.A CONFIGURATION EXV.B M.MST RSET *4 items skipped in this example. Table 26B — Configuring Return Temperature Reset MODE KEYPAD SUB-MODE...
  • Page 42: Demand Limit

    Under normal operation, the chiller will maintain a constant leaving fluid temperature approximately equal to the chilled fluid set point. As the cooler load varies, the entering cooler fluid will change in proportion to the load as shown in Fig. 20. Usually the chiller size and leaving-fluid temperature set point are selected based on a full-load condition.
  • Page 43: Cooling Set Point (4 To 20 Ma)

    DEMAND LIMIT (CCN Loadshed Controlled) — To con- figure Demand Limit for CCN Loadshed control set the De-  mand Limit Select (Configuration RSET Then configure the Loadshed Group Number (Configura-   tion RSET SHNM), Loadshed Demand Delta (Configu- ...
  • Page 44: Digital Scroll Option

    KEYPAD MODE SUB-MODE ENTRY CONFIGURATION DISP ENTER UNIT OPT1 OPT2 HP.A HP.B EXV.A EXV.B M.MST RSET *Seven items skipped in this example. The 30RAP units have a Digital Scroll Option — factory-installed option for a digital scroll compressor which provides additional stages of unloading for the unit. The digital compressor is always installed in the A1 compressor location.
  • Page 45: Start-Up And Operation

    See Fig. 23. An acceptable oil level in the compressors is from of sight glass. Adjust the oil level as re- quired. See Oil Charge section on page 50 for Carrier ap- proved oils. 6. Electrical power source must agree with unit nameplate.
  • Page 46: Operating Limitations

    CAUTION Brine duty application (below 40 F [4.4 C] LCWT) for chiller normally requires factory modification. Contact your Carrier representative for applicable LCWT range for standard water-cooled chiller in a specific application. VOLTAGE — ALL UNITS Main Power Supply — Minimum and maximum acceptable supply voltages are listed in the Installation Instructions.
  • Page 47: Service

    circuits, the control will most often start the A1 or B1 compres- sor first, especially after long off periods. The MBB controls fan stages to maintain the head pressure set point and will auto- matically adjust unit capacity as required to keep compressors from operating outside of the specified envelope.
  • Page 48 INCLUDED IN CABLE KIT CABLE CABLE RETAINER MOTOR ADAPTER ASSEMBLY GASKET SIGHTGLASS a30-4971 Fig. 24 — Electronic Expansion Valve Details During the next several seconds, carefully connect the nega- tive test lead to pins 1,2,4 and 5 in succession (plug J6 for Cir- cuit A, plug J7 for Circuit B).
  • Page 49: Compressor Replacement

    Fig. 25 — EXV Cable Connections to EXV Module b. Place a digital voltmeter, on 20-volt AC scale, across the black and white terminals on the con- troller. Restore power to the controller. For at least 7 seconds, the voltmeter should read approxi- mately 12 to 14 volts.
  • Page 50: Oil Charge

    Puron refrigerant systems use a polyol ester (POE) oil. Use only Carrier approved compressor oil. Oil should be visible in compressor oil sight glass. An acceptable oil level is from of sight glass. All compressors must be off when checking oil level.
  • Page 51 Fig. 26 — Compressor Location — 30RAP010-030 RGT SPT DISCHARGE ACCESS VALVE SIGHTGLASS DISCHARGE ACCESS VALVE Fig. 27 — Compressor Location — 30RAP035-060 SUCTION ACCESS VALVE COMPRESSOR A1 FLOW SWITCH SUCTION ACCESS VALVE FLOW SWITCH LEGEND FOR FIG. 26 AND 27 —...
  • Page 52: Check Unit Safeties

    Failure to provide the proper anti- freeze solution mixture is considered abuse and may impair or otherwise negatively impact the Carrier warranty. The main base board (MBB) monitors leaving fluid temper- ature at all times. The MBB will rapidly remove stages of ca- pacity as necessary to prevent freezing conditions due to the rapid loss of load or low cooler fluid flow.
  • Page 53: Pressure Transducers

    disconnected from J8. Compare the values determined with the value read by the control in the Temperatures mode using the scrolling marquee display. The suction and discharge Pressure Transducers — transducers are different part numbers and can be distinguished by the color of the transducer body, suction (yellow) and dis- charge (red).
  • Page 54 Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) VOLTAGE TEMP RESISTANCE DROP (Ohms) –25 3.699 98,010 –24 3.689 94,707 –23 3.679 91,522 –22 3.668 88,449 –21 3.658 85,486 –20 3.647 82,627 –19 3.636...
  • Page 55 Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) VOLTAGE TEMP RESISTANCE DROP (Ohms) –32 3.705 100,260 –31 3.687 94,165 –30 3.668 88,480 –29 3.649 83,170 –28 3.629 78,125 –27 3.608 73,580 –26 3.586...
  • Page 56 Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop VOLTAGE TEMP RESISTANCE DROP (Ohms) –25 4.758 196,453 –24 4.750 189,692 –23 4.741 183,300 –22 4.733 177,000 –21 4.724 171,079 –20 4.715 165,238 –19 4.705 159,717 –18 4.696 154,344 –17 4.686 149,194 –16...
  • Page 57 Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop VOLTAGE TEMP RESISTANCE DROP (Ohms) –32 4.762 200,510 –31 4.748 188,340 –30 4.733 177,000 –29 4.716 166,342 –28 4.700 156,404 –27 4.682 147,134 –26 4.663 138,482 –25 4.644 130,402 –24 4.624 122,807 –23...
  • Page 58 RGTA RGTB EVAPORATOR ENTERING FLUID TEMP EVAPORATOR LEAVING FLUID TEMP DPTB SPTB DPTA SPTA LEGEND ACCSY — Accessory — Discharge Pressure Transducer — Leaving Water Temperature Sensor — Low Voltage Terminal — Outdoor Air Temperature Sensor — Return Gas Temperature Sensor —...
  • Page 59 (EPM) chip to store the program parameters. This is an EEPROM memory chip and is accessible from the front of the VFD. It should not be removed with power applied to the VFD. LOSS OF CCN COMMUNICATIONS — Carrier Comfort Network ® (CCN) communications with external control systems can be affected by high frequency electrical noise gen- erated by the Motormaster V control.
  • Page 60: Wiring Diagram

    LOW AMBIENT OPERATION (MOTORMASTER V) HIGH SCCR ONLY a30-4977 LEGEND AUX — Auxiliary — Fuse Block MODE — Motormaster OFM — Outdoor Fan Motor — Terminal Block *208-v can run in mode 5 or 6. Fig. 32 — Typical Motormaster Wiring BUTTONS Mode Fig.
  • Page 61 FAULT CODE High Temperature Fault: Ambient temperature is too high; Cooling fan has failed (if equipped). Control Fault: A blank EPM, or an EPM with corrupted data has been installed. Incompatibility Fault: An EPM with an incompatible parame- ter version has been installed. CURRENT LIMIT: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current.
  • Page 62 Table 39 — Motormaster® V Program Parameters for Operating Modes PARAMETERS Line Voltage: 01 = low line, 02 = high line Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz Startup mode: flying restart Stop mode: coast to stop...
  • Page 63: Hydronic Package

    30RAP units are shipped with a single impeller size available for that pump. The pump was selected based on the flow and head requirements as provided to Carrier. It is not uncommon for actual pump duty to be different than what was anticipated at time of selection.
  • Page 64: Maintenance

    • Check condenser coils for debris, clean as necessary. Every month: • Check moisture indicating sight glass for possible refrig- erant loss and presence of moisture. Every 3 months (for all machines): • Check refrigerant charge. • Check all refrigerant joints and valves for refrigerant leaks, repair as necessary.
  • Page 65 High-Pressure Switch Trip — The high pressure switch has opened. Below are the factory settings for the fixed high pres- sure switch. CUTOUT 30RAP UNIT SIZE psig 010-060 4482 ASTP Protection Trip — All non-digital Copeland compres- sors are equipped with an advanced scroll temperature protec- tion (ASTP).
  • Page 66 SYMPTOMS Cooler Circulating Pump Does Power line open Not Run Control fuse or circuit breaker open Tripped power breaker Loose terminal connection Improperly wired controls Low line voltage Pump motor defective Pump seized Compressor Cycles Low refrigerant charge Off on Loss of Charge Compressor Cycles Off on Cooler Thermistor failure Freeze Protection...
  • Page 67: Alarm And Alert Codes

    ALARM/ ALARM ALERT DESCRIPTION CODE ALERT Circuit A, Compressor 1 T051 Alert Failure Circuit A, Compressor 1 A051 Alarm Failure Circuit A, Compressor 2 T052 Alert Failure Circuit A, Compressor 2 A052 Alarm Failure Circuit B, Compressor 1 T055 Alert Failure Circuit B, Compressor 1 A055...
  • Page 68 ALARM/ ALARM ALERT DESCRIPTION CODE ALERT T110 Alert Circuit A Loss of Charge T111 Alert Circuit B Loss of Charge Circuit A High Saturated T112 Alert Suction Temperature Circuit B High Saturated T113 Alert Suction Temperature Circuit A Low Suction T114 Alert Superheat...
  • Page 69 ALARM/ ALARM ALERT DESCRIPTION CODE ALERT Real Time Clock T153 Alert Hardware Failure Serial EEPROM A154 Alarm Hardware Failure Serial EEPROM T155 Alert Storage Failure Critical Serial EEPROM A156 Alarm Storage Failure A157 Alarm A/D Hardware Failure Loss of Communication A172 Alarm with EXV Board...
  • Page 70 ALARM/ ALARM ALERT DESCRIPTION CODE ALERT Flow Lost While Pump 2 T197 Alert Running Cooler Pump 1 Aux T198 Alert Contacts Closed While Pump Off Cooler Pump 2 Aux T199 Alert Contacts Closed While Pump Off Cooler Flow/Interlock T200 Alert Contacts Failed to Close at Start-Up Cooler Flow/Interlock...
  • Page 71 Alert Loss of Communication with Hydronic System Manager LEGEND FOR TABLE 42 — Carrier Comfort Network — Current Sensor Board EEPROM — Electronic Eraseable Programmable Read Only Memory — Energy Management Module — Entering Fluid Temperature — Electronic Expansion Valve —...
  • Page 72 IMPORTANT: If the CS is always detecting current, verify that the compressor is on. If the compressor is on, check the contactor and the relay on the MBB. If the compressor is off and there is no current, verify the CSB wiring and replace if necessary.
  • Page 73 rise to greater than the maximum SCT, the alert will occur and the circuit's remaining compressor will shut down. The cause of the alarm is usually an overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier, or a faulty high-pressure switch. T133 (Circuit A Low Suction Pressure) T134 (Circuit B Low Suction Pressure) —...
  • Page 74 APPENDIX A — DISPLAY TABLES Run Status Mode and Sub-Mode Directory SUB-MODE ITEM SETP CTPT LOD.F STAT VIEW LD.PM LS.AC MODE STGE ALRM TIME MNTH DATE YEAR HRS.U STR.U HR.P1 HR.P2 HRS.A HRS.B HOUR HR.A1 HR.A2 HR.B1 HR.B2 DISPLAY ITEM DESCRIPTION AUTO VIEW OF RUN STATUS xxx.x ºF Entering Fluid Temp...
  • Page 75 APPENDIX A — DISPLAY TABLES (cont) Run Status Mode and Sub-Mode Directory (cont) SUB-MODE ITEM ST.A1 STRT ST.A2 ST.B1 ST.B2 PUMP SI.PM P.1.DN P.2.DN P.1.MN P.2.MN PMDT P.1.M0 P.1.M1 P.1.M2 P.1.M3 P.1.M4 P.2.M0 P.2.M1 P.2.M2 P.2.M3 P.2.M4 STRN SI.ST S.T.DN S.T.MN ST.DT S.T.M0...
  • Page 76 APPENDIX A — DISPLAY TABLES (cont) Service Test Mode and Sub-Mode Directory SUB-MODE ITEM TEST EXV.A EXV.B FAN1 FAN2 FAN3 FAN4 FAN5 OUTS FAN6 V.HPA V.HPB CLP.1 CLP.2 UL.TM CL.HT RMT.A CC.A1 CMPA UL.TM CC.A2 CMPB CC.B1 CC.B2 Temperature Mode and Sub-Mode Directory SUB-MODE ITEM CEWT...
  • Page 77 APPENDIX A — DISPLAY TABLES (cont) Set Points Mode and Sub-Mode Directory SUB-MODE ITEM CSP.1 COOL CSP.2 CSP.3 H.DP F.ON HEAD F.OFF B.OFF F.DLT BR.FZ Inputs Mode and Sub-Mode Directory SUB-MODE ITEM STST FLOW PM.F.1 PM.F.2 GEN.I HT.RQ DLS1 DLS2 ICED DUAL FKA1...
  • Page 78 APPENDIX A — DISPLAY TABLES (cont) Outputs Mode and Sub-Mode Directory SUB-MODE ITEM FAN1 FAN2 FAN3 FAN4 FAN5 GEN.O FAN6 V.HPA V.HPB C.WP1 C.WP2 CLHT MLV.R EXV.A APPR AP.SP X.SH.R S.SH.R A.EXV SH_R OVR.A SPH.A ASH.S AMP.S PLM.A SPR.1 EXV.B APPR AP.SP OVR.B...
  • Page 79: Configuration Mode And Sub-Mode Directory

    APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory SUB-MODE ITEM TEST METR DISP LANG PAS.E PASS SIZE SZA.1 SZA.2 SZA.3 SZA.4 SZB.1 SZB.2 UNIT SZB.3 SZB.4 SH.SP FAN.S A1.TY MAX.T FLUD MLV.S CSB.E PM1E PM2E PM.P.S OPT1 PM.SL PM.DY PM.DT...
  • Page 80 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM CTRL LOAD LLCS OPT2 LCWT DELY ICE.M LS.MD LS.ST LS.ND LS.LT CCNA CCNB BAUD A1.DT HP.A A2.DT B1.DT HP.B B2.DT DISPLAY ITEM DESCRIPTION UNIT OPTIONS 2 CONTROLS Control Method Loading Sequence Select Lead/Lag Circuit Select...
  • Page 81 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM STR.A MIN.A RNG.A SPD.A POF.A MIN.A MAX.A OVR.A EXV.A TYP.A H.SCT X.PCT X.PER A.PCT M.PCT S.PCT DELY STR.B MIN.B RNG.B SPD.B EXV.B POF.B MIN.B MAX.B OVR.B TYP.B DISPLAY ITEM DESCRIPTION...
  • Page 82 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM MMR.S P.GAN I.GAN D.GAN MIN.S CRST MA.DG RM.NO RM.F RM.DG RT.NO RT.F RT.DG DMDC RSET DM20 SHNM SHDL SHTM DLS1 DLS2 LLEN MSSL SLVA LLBL LLBD LLDY PARA DISPLAY...
  • Page 83 APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE ITEM CLSP SLCT RL.S CRMP SCHD Z.GN EN.A1 SERV EN.A2 EN.B1 EN.B2 T.D.B BCST OAT.B G.S.BC BC.AK DISPLAY ITEM DESCRIPTION SETPOINT AND RAMP LOAD Cooling Set Point Select ENBL/DSBL Ramp Load Select ENBL/DSBL...
  • Page 84 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory SUB-MODE ITEM TIME HH.MM MNTH DATE YEAR STR.M STR.W STR.D MIN.A STP.M STP.W STP.D MIN.S HOL.L HD.01 HD.02 HD.03 HD.04 HD.05 HD.06 HD.07 HD.08 DISPLAY ITEM DESCRIPTION TIME OF DAY XX.XX Hour and Minute MONTH, DATE, DAY, AND YEAR...
  • Page 85 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM HD.09 HD.10 HD.11 HD.12 HD.13 HD.14 HD.15 HD.16 HD.17 HD.18 HD.19 DISPLAY ITEM DESCRIPTION HOLIDAY SCHEDULE 09 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 10 Holiday Start Month Start Day Duration (days)
  • Page 86 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM HD.20 HD.21 HD.22 HD.23 HD.24 HD.25 HD.26 HD.27 HD.28 HD.29 HD.30 DISPLAY ITEM DESCRIPTION HOLIDAY SCHEDULE 20 Holiday Start Month Start Day Duration (days) HOLIDAY SCHEDULE 21 Holiday Start Month Start Day Duration (days)
  • Page 87 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM SCH.N SCH.L OCC.1 UNC.1 MON.1 TUE.1 PER.1 WED.1 THU.1 FRI.1 SAT.1 SUN.1 HOL.1 OCC.2 UNC.2 MON.2 TUE.2 PER.2 WED.2 THU.2 FRI.2 SAT.2 SUN.2 HOL.2 OCC.3 UNC.3 MON.3 TUE.3...
  • Page 88 APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE ITEM OCC.6 UNC.6 MON.6 TUE.6 PER.6 WED.6 THU.6 FRI.6 SAT.6 SUN.6 HOL.6 OCC.7 UNC.7 MON.7 TUE.7 PER.7 WED.7 THU.7 FRI.7 SAT.7 SUN.7 HOL.7 OCC.8 UNC.8 MON.8 TUE.8 PER.8 WED.8...
  • Page 89 APPENDIX A — DISPLAY TABLES (cont) Operating Mode and Sub-Mode Directory SUB-MODE ITEM MD01 MD02 MD03 MD05 MD06 MD07 MD08 MD09 MD10 MD13 MODE MD14 MD15 MD16 MD17 MD18 MD19 MD20 MD21 MD22 MD23 MD24 MD25 Alarms Mode and Sub-Mode Directory SUB-MODE ITEM AXXX...
  • Page 90 CCN DISPLAY TABLES — A_UNIT (General Unit Parameters) DESCRIPTION Control Mode 0 = Test 1 = Local Off 2 = CCN Off 3 = Clock Off 4 = Emergency Stop 5 = Local On 6 = CCN On 7 = Clock On 8 = Heat Enabled 9 = Pump Delay Occupied...
  • Page 91 CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs) DESCRIPTION CIRC. A DISCRETE OUTPUTS Compressor A1 Relay Compressor A2 Relay Minimum Load Valve Relay CIRC. A DISCRETE INPUTS Compressor A1 Feedback Compressor A2 Feedback CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Parameters) DESCRIPTION CIRCUIT B ANALOG VALUES Percent Total Capacity...
  • Page 92 CCN DISPLAY TABLES — OPTIONS (Unit Parameters) DESCRIPTION FANS Fan 1 Relay Fan 2 Relay Cooler/Pump Heater UNIT ANALOG VALUES Cooler Entering Fluid Cooler Leaving Fluid Lead/Lag Leaving Fluid TEMPERATURE RESET 4-20 mA Reset Signal Outside Air Temperature Space Temperature DEMAND LIMIT 4-20 mA Demand Signal Demand Limit Switch 1...
  • Page 93 CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration) DESCRIPTION Control Method 0 = Switch 2 = Occupancy 3 = CCN Loading Sequence Select 1 = Equal Loading 2 = Staged Loading Lead/Lag Circuit Select 1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads Cooling Setpoint Select 0 = Single...
  • Page 94 CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings) DESCRIPTION LEAD/LAG Lead/Lag Chiller Enable Master/Slave Select Slave Address Lead/Lag Balance Select Lead/Lag Balance Delta Lag Start Delay Parallel Configuration CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP) DESCRIPTION VALUE Service Password nnnn Password Enable Enable/Disable...
  • Page 95 APPENDIX B — CCN TABLES (cont) DESCRIPTION SERVICE Brine Freeze Point Pump Service Interval COMPRESSOR ENABLE Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 DESCRIPTION COOLING Cooling Setpoint 1 Cooling Setpoint 2 ICE Setpoint RAMP LOADING Cooling Ramp Loading Brine Freeze Point Head Setpoint...
  • Page 96 CCN MAINTENANCE TABLES — CIRB_EXV DESCRIPTION EXV % Open Circuit B Approach Approach Setpoint EXVB Override Suction Superheat Temp Active Superheat Setpt Active MOP Setpt Cir B EXV Position Limit CCN MAINTENANCE TABLES — STRTHOUR DESCRIPTION Machine Operating Hours Machine Starts Circuit A Run Hours Compressor A1 Run Hours Compressor A2 Run Hours...
  • Page 97 CCN MAINTENANCE TABLES — ALARMS DESCRIPTION Active Alarm #1 Active Alarm #2 Active Alarm #3 Active Alarm #4 Active Alarm #5 Active Alarm #6 Active Alarm #7 Active Alarm #8 Active Alarm #9 Active Alarm #10 Active Alarm #11 Active Alarm #12 Active Alarm #13 Active Alarm #14 Active Alarm #15...
  • Page 98 DESCRIPTION Pump Service Interval Pump 1 Service Countdown Pump 1 Maintenance Done Pump 2 Service Countdown Pump 2 Maintenance Done Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date...
  • Page 99 CCN MAINTENANCE TABLES — RUNTEST DESCRIPTION Percent Total Capacity Percent Available Cap. Discharge Pressure Suction Pressure Head Setpoint Saturated Condensing Tmp Saturated Suction Temp Compr Return Gas Temp Discharge Gas Temp Suction Superheat Temp Compressor A1 Relay Compressor A2 Relay Minimum Load Valve Relay Compressor A1 Feedback Compressor A2 Feedback...
  • Page 100 DESCRIPTION Dual Chiller Link Good? Master Chiller Role Slave Chiller Role Lead Chiller Ctrl Point Lag Chiller Ctrl Point Control Point Cool EnteringFluid-Slave Cool Leaving Fluid-Slave Cooler Entering Fluid Cooler Leaving Fluid Lead/Lag Leaving Fluid Percent Avail.Capacity Percent Avail.Cap.Slave Lag Start Delay Time Load/Unload Factor Load/Unload Factor-Slave Lead SMZ Clear Commanded...
  • Page 101 APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS PUMP OPTION PUMP SIZE 1, 8 1.0 HP 2, 9 1.5 HP 3, B 2.0 HP 4, C 3.0 HP 5, 6, D, F 5.0 HP 7, G 7.5 HP UNIT VOLTAGE V-Hz (3 Ph) 208/230-60...
  • Page 102 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING Optional BACnet Communications Wiring — The following section is used to configure the UPC Open con- troller which is used when the BACnet communications option is selected. The UPC Open controller is mounted in the main control box per unit components arrangement diagrams.
  • Page 103 EIA-485 and 2W. The example in Fig. C shows the BAS Port DIP Switches set for 76.8k (Carrier default) and MS/TP. Set the BAS Port DIP Switches DS2 and DS1 for the appro- priate communications speed of the MS/TP network (9600, 19.2k, 38.4k, or 76.8k bps).
  • Page 104 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) To install a BT485 terminator, push the BT485 terminator on to the BT485 connector located near the BACnet connector. NOTE: The BT485 terminator has no polarity associated with To order a BT485 terminator, consult Commercial Products i-Vu Open Control System Master Prices.
  • Page 105 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table D — Open System Wiring Specifications and Recommended Vendors WIRING SPECIFICATIONS Wire Type 22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications.
  • Page 106 3 UPC Open controllers on a CCN bus. For the CCN Alarm Acknowledger configuration, the UPC Open defaults to CCN Acknowledger. If a Chiller Lead/Lag/ Standby application is being used, then the Carrier technician must change the configuration to only one CCN Acknowledger on the CCN bus.
  • Page 107 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) CCN POINT POINT DESCRIPTION NAME 4-20 ma Demand Signal LMT_MA 4-20 ma Reset Signal RST_MA Active Demand Limit DEM_LIM Active Setpoint Alarm State CCN Chiller CHIL_S_S CCN Loadshed Signal DL_STAT Circuit A Run Hours HR_CIRA Circuit A Starts CY_CIRA...
  • Page 108 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) POINT DESCRIPTION POINT NAME Cooling Setpoint 2 CSP2 CSM Controlling Chiller MODE_1 Demand Level 1 Demand Level 2 Demand Level 3 Demand Limit Switch 1 DMD_SW1 Demand Limit Switch 2 DMD_SW2 Demand/Sound Limited MODE_15 Discharge Gas Temp DISGAS...
  • Page 109 APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) POINT DESCRIPTION POINT NAME Percent Total Capacity CAP_T Percent Total Capacity CAPA_T Percent Total Capacity CAPB_T Pump 1 Maintenance Done P1_MAINT Pump 1 Run Hours HR_PUMP1 Pump 1 Service Countdown P1_CDOWN Pump 2 Maintenance Done P2_MAINT Pump 2 Run Hours HR_PUMP2...
  • Page 110 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS Compressor Check oil level. Cooler None. Condenser None. Compressor Check oil level. Cooler None. Condenser None. Compressor Check oil level Check refrigerant charge. Check all connec- Cooler tions for leaks. Condenser None. Check Oil Level.
  • Page 111 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) Plant ___________________________ Machine Model No. ________________ CHECK ALARMS DATE OIL LEVEL / FAULTS NOTE: Equipment failures caused by lack of adherence to the Main- tenance Interval Requirements are not covered under warranty. 30RAP Weekly Maintenance Log OPERATOR INITIALS...
  • Page 112 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) Month Date Operator UNIT SECTION ACTION Check Oil Level Compressor Send Oil Sample Out for Analysis Leak Test Inspect and Clean Cooler Inspect Cooler Heater Cooler Leak Test Record Water Pressure Differential (PSI) Inspect Water Pumps Leak Test Condenser...
  • Page 113 APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) Month Date Operator UNIT SECTION ACTION Isolate and Drain Cooler Cooler Add Glycol for Freeze Protection Controls Do Not Disconnect Control Power NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
  • Page 114 Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 114 12-10 Replaces: 30RAP-1T...
  • Page 115 START-UP CHECKLIST FOR 30RAP LIQUID CHILLER I. Project Information JOB NAME ______________________________________________________________________________ ADDRESS _______________________________________________________________________________ CITY ____________________________________________ STATE _______________ ZIP______________ INSTALLING CONTRACTOR ________________________________________________________________ SALES OFFICE ___________________________________________________________________________ START-UP PERFORMED BY ________________________________________________________________ Design Information CAPACITY CEAT UNIT MODEL ______________________________ SERIAL ________________________________ II. Preliminary Equipment Check IS THERE ANY PHYSICAL DAMAGE? DESCRIPTION ____________________________________________________________________________ ________________________________________________________________________________________...
  • Page 116 5. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER. 6. CHILLED WATER FLOW SWITCH IS OPERATIONAL. 7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40). 8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C). ANTIFREEZE TYPE _____________________ CONCENTRATION __________%. IF OUTDOOR AMBIENT IS BELOW 32 F (0°...
  • Page 117 OPERATING DATA: RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN MACHINE IS IN A STABLE OPERATING CONDITION: PRESSURE/TEMPERATURE DISCHARGE PRESSURE SUCTION PRESSURE SATURATED CONDENSING TEMP SATURATED SUCTION TEMP RETURN GAS TEMPERATURE LIQUID LINE TEMPERATURE* DISCHARGE LINE TEMPERATURE* *Readings taken with a digital thermometer.
  • Page 118 Record Software Versions MODE — RUN STATUS SUB-MODE ITEM DISPLAY VERS AUX1 MARQUEE NAVIGATOR (PRESS ENTER AND ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS) COMMENTS: _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________...
  • Page 119 III. Unit Start-Up (cont) RECORD CONFIGURATION SETTINGS SUBMODE ITEM SIZE SZA.1 SZA.2 SZA.3 SZA.4 SZB.1 UNIT SZB.2 SZB.3 SZB.4 SH.SP FAN.S A1.TY MAX.T PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW: SUBMODE ITEM FLUD...
  • Page 120 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. SUBMODE ITEM CTRL LOAD LLCS LCWT DELY ICE.M OPT2 CLS.C LS.MD LS.ST LS.ND LS.LT CTRL CCNA CCNB PRESS ESCAPE KEY TO DISPLAY ‘OPT2’.
  • Page 121 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘HP.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.A’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. SUB-MODE RNG.A MAX.A OVR.A EXV.A H.SCT X.PER M.PCT PRESS ESCAPE KEY TO DISPLAY ‘EXV.A’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.B’. PRESS ENTER KEY.
  • Page 122 III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘MM’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. SUBMODE ITEM RSET CRST MA.DG RM.NO RM.F RM.DG RT.NO RT.F RT.DG DMDC DM20 SHNM SHDL SHTM DLS1 DLS2 LLEN...
  • Page 123 III. Unit Start-Up (cont) PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS. RECORD CONFIGURATION INFORMATION BELOW: SUBMODE ITEM COOL CSP.1 CSP.2 CSP.3...
  • Page 124 NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed. Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Table of Contents