[ II Restrictions ]

[5] An Example of a System to which an MA Remote Controller is connected

1. System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
L1
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW2-1 OFF
SW2-1 OFF
OS2
00
TB3
TB7
TB3
M1 M2
M1 M2
S
M1 M2
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 200 model or above is connected) are con-
nected.
4) Automatic address setup is not available if start-stop in-
put (CN32, CN51, CN41) is used for a group operation of
indoor units. Refer to "[5] 2. Manual address setup for
both indoor and outdoor units".(page 32)
5) To connect more than 2 LOSSNAY units to indoor units
in the same system, refer to "[5] 2. An example of a sys-
tem with one outdoor unit to which 2 or more LOSSNAY
units are connected".(page 32)
HWE10130
L2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS1
OC
00
00
TB3
TB7
TB7
M1 M2
S
M1 M2
M1 M2
S
Group
A B
MA
L3
Group
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A B
MA
L12
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A B
A B
MA
MA
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L1 +L2+L3+L4 200m[656ft]
L1 +L2+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
- 30 -
Interlock operation with
the ventilation unit
L4
LC
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
A B
RC
MA
L13
IC
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
MA
m3
2
[AWG16] or larger)
2
[AWG22 to 16])
TB15
1 2
GB