[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10130
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-RP300YJM-B
27°C/19°C
[81°F/66°F]
35°C/- [95°F/- ]
4
Unit
4
-
125/80/63/32
10 [32-3/4]
5 [16-3/8]
30 [98]
-
Hi
kg
14.3 [32]
A
16.6
V
400
Hz
78
293/228/397/168
295
1400
2.86/0.84
[415/122]
73 [163]
43 [109]
14 [57]
13 [55]
26 [79]
13 [55]
33 [91]
8 [46]
10 [50]
- 124 -
Outdoor unit model
PUHY-RP350YJM-B
27°C/19°C
[81°F/66°F]
35°C/- [95°F/- ]
4
4
140/125/63/32
10 [32-3/4]
5 [16-3/8]
30 [98]
Hi
15.6 [35]
19.9
400
95
336/345/397/235
322
1400
2.95/0.82
[428/119]
75 [167]
45 [113]
12 [54]
12 [54]
28 [82]
12 [54]
32 [90]
6 [43]
8 [46]
GB