[ II Restrictions ]
2) Remote controller wiring
Type
Number of
cores
Cable type
Cable size
Maximum overall line
length
*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and
wireless remote controller.
*2 ME remote controller refers to ME remote controller and ME simple remote controller.
*3 The use of cables that are smaller than 0.75mm
*4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
HWE10130
MA remote controller
CVV
2-core cable
2 *3
0.3 to 1.25mm
[AWG22 to 16]
2
*4
(0.75 to 1.25mm
)
[AWG18 to 16]
200 m [656ft] max.
2
(AWG18) is recommended for easy handling.
- 17 -
*1
ME remote controller
CVV
2-core cable
0.3 to 1.25mm
[AWG22 to 16]
(0.75 to 1.25mm
[AWG18 to 16]
The section of the cable that exceeds 10m
[32ft] must be included in the maximum in-
door-outdoor transmission line distance.
*2
2 *3
2
*4
)
GB