[ II Restrictions ]
(2) Using a branch joint to merge the existing piping systems
Piping in a non-REPLACE MULTI system
Indoor
Indoor
1
2
Total pipe length
Total pipe length (L) from the outdoor unit
to the farthest indoor unit
Piping length
Total pipe length from the first branch to
the farthest indoor unit ( )
Between indoor and
Height
outdoor units
difference
Between indoor units
1) The maximum allowable piping length for the RP650 through RP900 models is 250 m [820 ft].
Observe the piping length limitation imposed by the refrigerant amount as calculated with the formula below.
PUHY-RP200 - RP250YJM: 0.39 × L
PUHY-RP300 - RP900Y(S)JM: 0.39 × L
PUHY-RP200 - RP250YJM: 4.20× L
PUHY-RP300 - RP900Y(S)JM: 4.20× L
L
: Length of ø22.2 liquid pipe (m)
0
L
: Length of ø19.05 liquid pipe (m)
1
L
: Length of ø15.88 liquid pipe (m)
2
L
: Length of ø12.7 liquid pipe (m)
3
L
: Length of ø9.52 liquid pipe (m)
4
L
: Length of ø6.35 liquid pipe (m)
5
2) The maximum allowable piping length for the RP650 through RP900 models is 100 m [328 ft] (Equivalent length: 125 m [410
ft])
3) The piping length difference between the two piping systems that are merged with a branch joint should be 40 m [131 ft] or
less.
HWE10130
Indoor
Indoor
3
4
Operation
Outdoor unit
above indoor unit
Outdoor unit be-
low indoor unit
+ 0.29 × L
+ 0.2 × L
0
1
+ 0.29 × L
0
1
' + 3.12× L
' + 2.15 × L
0
1
' + 3.12× L
0
1
Piping in a REPLACE MULTI system
Outdoor unit
First branch
B
(Branch joint)
a
b
Indoor
Indoor
1
2
Pipe sections
A+B+C+a+b+c+d
A+C+d
or
A+B+b
B+b
or
C+d
H
H'
h
+ 0.12 × L
+ 0.06 × L
2
3
+ 0.2 × L
+ 0.12 × L
+ 0.06 × L
2
3
' + 1.29 × L
' + 0.65 × L
2
3
' + 2.15 × L
' + 1.29 × L
' + 0.65 × L
2
3
L
' : Length of ø22.2 [7/8"] liquid pipe [ft]
0
L
' : Length of ø19.05 [3/4"] liquid pipe [ft]
1
L
' : Length of ø15.88 [5/8"] liquid pipe [ft]
2
L
' : Length of ø12.7 [1/2"] liquid pipe [ft]
3
L
' : Length of ø9.52 [3/8"] liquid pipe [ft]
4
L
' : Length of ø6.35 [1/4"] liquid pipe[ft]
5
- 51 -
A
C
c
d
Indoor
Indoor
3
4
Allowable length of pipes
300 [984] or less (Note 1)
120 [393] or less
(Equivalent length 150 [492]or less)
(Note 2)
100 [328] or less (Note 3)
50 [164] or less
40 [131] or less
15 [49] or less
+ 0.024 × L
< 18 (kg)
4
5
+ 0.024 × L
< 25 (kg)
4
5
' + 0.26 × L
' < 40 [oz]
4
5
' + 0.26 × L
' < 56 [oz]
4
5
Unit: m [ft]
GB