Mitsubishi Electric PUHY-RP200 Service Handbook page 226

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
4.
Long piping length
The cooling capacity varies greatly depending on the
pressure loss. (When the pressure loss is large, the
cooling capacity drops.)
5.
Piping size is not proper (thin)
6.
Insufficient refrigerant amount
Protection works and compressor frequency does
not rise due to high discharge temperature.
7.
Clogging by foreign object
8.
The indoor unit inlet temperature is excessively.
(Less than 15°C [59°F] WB)
9.
Compressor failure
The amount of circulating refrigerant decreases due
to refrigerant leak in the compressor.
10.
LEV1 malfunction
Sufficient liquid refrigerant is not be supplied to the
indoor unit as sufficient sub cool cannot be secured
due to LEV1 malfunction.
11.
TH3, TH6 and 63HS1 sensor failure or faulty wiring
LEV1 is not controlled normally.
12.
LEV2 actuation failure
A drop in the low pressure that is caused either by a
blockage of liquid pipe or by a pressure loss and the
resultant slowing of refrigerant flow causes a tenden-
cy for the discharge temperature to rise.
HWE10130
Cause
Check method and remedy
Check the piping length to determine if it is contrib-
uting to performance loss.
Piping pressure loss can be estimated from the
temperature difference between the indoor unit
heat exchanger outlet temperature and the satura-
tion temperature (Te) of 63LS. ->Correct the piping.
Refer to 1-1. (Compressor frequency does not rise
sufficiently.)Refer to the page on refrigerant amount
adjustment
Check the temperature difference between in front
of and behind the place where the foreign object is
clogging the pipe (upstream side and downstream
side). When the temperature drops significantly, the
foreign object may clog the pipe.
-> Remove the foreign object inside the pipe.
Check the inlet air temperature and for short cy-
cling. Change the environment where the indoor
unit is used.
Check the discharge temperature to determine if
the refrigerant leaks, as it rises if there is a leak.
Refer to the page of LEV troubleshooting
([4] -5-).(page 228)
It most likely happens when there is little difference
or no difference between TH3 and TH6.
Check the thermistor.
Check wiring.
Refer to the page on troubleshooting the LEV ([4] -
5-).(page 228)
- 217 -
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents