Mitsubishi Electric PUHY-RP200 Service Handbook page 144

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10130
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-RP250YJM-B
-
-
kg
A
V
Hz
70
-
-
2.79/0.73
[405/106]
79 [174]
10 [50]
2 [36]
3 [37]
3 [37]
21 [70]
35 [95]
67 [153]
- 135 -
Outdoor unit model
PUHY-RP500YSJM-B
PUHY-RP250YJM-B
20°C/- [68°F/- ]
7°C/6°C
[45°F/43°F]
4
4
250/125/100/32
10 [32-3/4]
5 [16-3/8]
30 [98]
Hi
26.1 [58]
25.6
400
70
380/386/315/241
2.79/0.73
[405/106]
79 [174]
10 [50]
2 [36]
3 [37]
3 [37]
21 [70]
35 [95]
67 [153]
-
-
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents