[ II Restrictions ]

[1] System configuration

II Restrictions
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
Outdoor
Composing units
units
200
-
250
-
300
-
350
-
400
200
450
200
500
250
550
250
600
300
650
300
700
200
750
250
800
250
850
250
900
300
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE10130
Maximum total capacity
of connectable indoor
-
-
-
-
-
-
-
-
200
-
250
-
250
-
300
-
300
-
350
-
250
250
250
250
250
300
400 - 1040
300
300
425 - 1105
300
300
450 - 1170
Maximum number
of connectable in-
units
door units
100 - 260
125 - 325
150 - 390
175 - 455
200 - 520
225 - 585
250 - 650
275 - 715
300 - 780
325 - 845
350 - 910
375 - 975
- 15 -
Types of connectable in-
door units
17
P15 - P250 models
R410A series indoor units
21
26
30
32
32
32
32
32
32
32
32
32
32
32
GB