[ VII Control ]
Switch
Function
1
2
Model selection
3
4
Low-noise mode
5
selection
SW5
6
7
Model selection
8
9
Automatic refriger-
10
ant charging
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) When set to the capacity priority mode and if the following conditions are met, the Low-noise mode will terminate, and the unit
will go back into the normal operation mode.
Cooling: Outside temperature is high or high pressure is high.
Heating: Outside temperature is low or low pressure is low.(page 25)
4) The table below summarizes the factory settings for dipswitches SW5-1 through SW5-4, and SW5-7. The factory setting for
all other dipswitches is OFF.
5) The refrigerant oil recovery operation can be cancelled and normal operation can be started if Stage 3 in the cooling mode or
Stage 4 in the heating mode has been completed. To cancel the operation, set the SW4-7 to OFF.
1
OFF
ON
OFF
OFF
OFF
(2) INV board
Functions are switched with the following connector.
Connector
CN6 short-
Enabling/disabling the following error
circuit con-
detection functions;
nector
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
(5301 Detail No.117)
IPM open/ACCT erroneous wiring
(5301 Detail No. 119)
Detection of ACCT erroneous wiring
(5301 Detail No.120)
CN6 short-circuit connector is mated with the mating connector.
Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
HWE10130
Function according to switch setting
OFF
See the table below (Note 4)
Capacity priority
mode (Note 3)
-
-
See the table below (Note 4)
-
-
-
-
Normal control
SW 5
2
3
ON
OFF
ON
OFF
ON
ON
ON
Function
ON
Low-noise mode
-
-
-
Starts automatic re-
frigerant charging
4
7
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Function according to connec-
tor
Enabled
Disabled
Error detec-
Error detec-
tion enabled
tion disable
(No load op-
eration is pos-
sible.)
- 91 -
Switch setting timing
OFF
ON
Before being energized
Before being energized
-
Before being energized
-
-
Any time after being ener-
gized
model
RP200 model
RP250 model
RP300 model
RP350 model
Setting timing
Enabled
Anytime after power on
Units that re-
quire switch
setting
Note.2
OC
OS
C
C
A
-
-
-
B
B
-
-
-
-
A
-
Disabled