An Example Of A System To Which An Ma Remote Controller Is Connected - Mitsubishi Electric PURY-(E)P200 Service Handbook

Hide thumbs Also See for PURY-(E)P200:
Table of Contents

Advertisement

[ II Restrictions ]

[5] An Example of a System to which an MA Remote Controller is connected

1. System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
L1
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW2-1 OFF
SW2-1 OFF
OS
00
TB3
TB7
TB3
M1 M2
M1 M2
S
M1 M2
*1. When BS is connected to the system,
automatic address setup is not available.
(2) Cautions
1) M-NET remote controller and MA remote controller can-
not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) When the number of the connected indoor units is as
shown in the table below, one or more transmission
boosters (sold separately) are required.
To connect two transmission boosters, connect them in
parallel. (Observe the maximum number of connectable
indoor units that are listed in the specifications for each
outdoor unit.)
When the P200 and P250 mod-
els are not included in the con-
nected indoor units
When the P200 and P250 mod-
els are included in the connect-
ed indoor units
The table above shows the number of transmission
boosters that is required by the system with three BC
controllers. For each BC controller that is subtracted
from the above-mentioned system, two additional indoor
units can be connected.
HWE07130
L2
L3
OC
BC
00
00
TB02
TB7
M1 M2
S
M1 M2 S
*1
M1M2
S
TB02
00
Group
BS
A1 B2
MA
Number of transmission
booster (sold separately) re-
quired
1 unit
2 units
27 - 50 units
21 - 39 units
40 - 50 units
L4
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
MA
L12
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
A1 B2
MA
MA
4) Automatic address setup is not available if start-stop in-
put(CN32, CN51, CN41) is used for a group operation of
indoor units. Refer to "[5] 2. Manual address setup for
both indoor and outdoor units"
5) To connect more than 2 LOSSNAY units to indoor units
in the same system, refer to the next section "[5] 2. An
example of a system with one outdoor unit to which 2 or
more LOSSNAY units are connected".
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L1 +L2+L3+L4+L5 200m[656ft]
L1 +L2+L3+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
-
(0.3 to 1.25mm
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
- 26 -
Interlock operation with
the ventilation unit
L5
Group
LC
IC
00
00
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A1 B2
A1 B2
RC
MA
L13
Group
IC
IC
00
00
TB5
TB15
TB5
M1 M2
M1 M2
S
1 2
S
A1 B2
MA
m3
2
[AWG16] or larger)
2
[AWG22 to 16])
TB15
1 2
GB