[ II Restrictions ]

[3] An Example of a System to which an MA Remote Controller is connected

1. System with one outdoor unit (Heat source unit) (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
L1
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
00
TB3
TB7
M1 M2
M1 M2
S
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) When the number of the connected indoor units is as
shown in the table below, one or more transmission
boosters (sold separately) are required.
To connect two transmission boosters, connect them in
parallel. (Observe the maximum number of connectable
indoor units that are listed in the specifications for each
outdoor unit.)
When the P72 and P96 models
are not included in the connect-
ed indoor units
When the P72 and P96 models
are included in the connected
indoor units
HWE2206A
L2
Group
HB
IC
00
00
TB5
TB15
TB02
M1 M2
S
1 2
M1 M2 S
A1 B2
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
A1 B2
A1 B2
MA
MA
Number of transmission
booster (sold separately) re-
quired
1 unit
2 units
27 - 50 units
-
21 - 39 units
40 - 50 units
- 23 -
L3
L4
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
A1 B2
MA
RC
MA
L12
L13
Group
IC
00
TB5
TB15
M1 M2
S
1 2
A1 B2
MA
MA
4) Automatic address setup is not available if start-stop in-
put(CN32, CN51, CN41) is used for a group operation of
indoor units.
5) No more than 2 HBC controllers can be connected.
Sub-HBC controller cannot be connected.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L1 +L2+L3+L4 200m[656ft]
L1 +L2+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
2
(0.3 to 1.25mm
[AWG22 to 16])
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
23
Interlock operation with
the ventilation unit
LC
00
TB5
M1 M2
S
IC
00
TB5
TB15
M1 M2
S
1 2
m3
2
[AWG16] or larger)